| 2005-08-13 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY (CHANGE OF USE).THE PLANS |
| | MUST BE STAMPED AND THE RECEIPT ATTACHED |
| | TO THE APPLICATION. 233-5025 |
| | |
| | 3.)PLEASE CONTACT JOHN HIGGINS IN |
| | REGARDS TO ADDRESSING FOR THIS PARCEL. |
| | OUR RECORDS CONFLICT WITH THE ADDRESS ON |
| | YOUR APPLICATION.HE CAN BE REACHED AT |
| | 805-1239.***NOTE 8/16 - J.HIGGINS |
| | CHANGED OUR RECORDS TO REFLECT 5760 |
| | CORPORATE WAY AS CORRECT ADDRESS FOR |
| | THIS PARCEL*** |
| | |
| | 4.)GENERAL NOTES, ITEM 12 ON THE |
| | SURVEY PREPARED BY TARGET SURVEYING, |
| | INC. STATES THAT THE SURVEY WILL NOT BE |
| | USED FOR CONSTRUCTION OR PERMITTING. |
| | SUBMIT A SURVEY FOR PERMITTING. |
| | |
| | 5.)THE SURVEYOR IS REQUIRED TO DATE |
| | THE SEAL, FS472.025, SEE ATTACHED.THE |
| | SEAL IS TO BE LEGIBLE. |
| | |
| | 5.)THIS PARCEL IS IN A FLOOD ZONE.A |
| | FORM BOARD ELEVATION CERTIFICATE WILL BE |
| | REQUIRED.THE FINISHED FLOOR IS TO BE |
| | SIX INCHES ABOVE BASE FLOOD ELEVATION, |
| | CITY OF WEST PALM BEACH MUNICIPAL CODE |
| | 94-546(2). NOTE MINIMUM ELEVATION ON THE |
| | PLAN. |
| | |
| | 6.)SIGN THE OWNER/AGENT LINE OF THE |
| | ENERGY CALCS. |
| | |
| | 7.)A WAREHOUSE SHOULD BE S OCCUPANCY, |
| | THE OFFICE AREA IS B.PLEASE SEE FBC312 |
| | AND FBC305.BUSINESS OCCUPANCY WAS |
| | DECLARED ON SHEET A2. |
| | |
| | 8.)PROVIDE A SITE PLAN, FBC*104.3.1.1. |
| | SHOW ALL DISTANCES FROM THE PROPERTY |
| | LINE SO THAT TABLE 500 AND TABLE 600 |
| | COMPLIANCE CAN BE DETERMINED.SHOW |
| | ACCESSIBLE PARKING, ACCESSIBLE ROUTE |
| | FROM THE PUBLIC WAY FBC CHAPTER 11. |
| | |
| | 9.)THE AREA INCREASE CALCULATIONS ON |
| | A2 STATES THAT THE ALLOWABLE AREA FOR |
| | BUSINESS TYPE V IS 9000 SF.PLEASE NOTE |
| | THAT IT IS 14000 SF PER FBC TABLE 500 |
| | AND 16000 FOR STORAGE. |
| | |
| | 10.)TYPE V CONSTRUCTION IS TO HAVE |
| | NONCOMBUSTIBLE WALLS.THE PARAPET AND |
| | THE WALL BELOW THE HIP ROOF SHOWS WOOD |
| | SHEATHING.SEVERAL DETAILS ARE |
| | AFFECTED; 2-A3, D-A4.CHECK ALL |
| | DETAILS. |
| | |
| | 11.)DOOR 3 APPEARS TO BLOCK OVER HALF |
| | THE WIDTH OF THE HALLWAY, FBC1012.1.4. |
| | |
| | 12.)CLARIFY THE ROOF AREA ON A3. |
| | |
| | 13.)DOOR HARDWARE TO COMPLY WITH |
| | FBC11-4.13.9. |
| | |
| | 14.)PROVIDE A SOILS INVESTIGATION |
| | REPORT. |
| | |
| | 15.)PROVIDE LEGIBLE NOAS.THEY ARE |
| | AVAILABLE EITHER AT WWW.MIAMIDADE.GOV |
| | (FIND A DEPT, BUILDING CODE COMPLIANCE, |
| | PRODUCT CONTROL) OR AT |
| | WWW.FLORIDABUILDING.ORG (PRODUCT |
| | APPROVAL). |
| | |
| | 16.)THE FOLLOWING NOAS WERE REVIEWED |
| | AND APPEAR CODE COMPLIANT EXCEPT AS |
| | NOTED BUT REQUIRE FLORIDA STATE OR LOCAL |
| | PRODUCT APPROVALS, FAC9B72. |
| | WWW.FLORIDABUILDING.ORG. |
| | |
| | ARCH ALUMINUM IMPACT WALL 3000 |
| | ARCH ALUMINUM MAGNUM STILE ENTRANCE DOOR |
| | MODEL 651 ROLLING DOOR ? EXPIRED NOA |
| | |
| | 17.)PROVIDE PRODUCT APPROVALS FOR THE |
| | REAR METAL DOOR, FLAT ROOF, STANDING |
| | SEAM, ROLLING DOOR.ANY PRODUCT |
| | APPROVALS NOT REVIEWED PRIOR TO PERMIT |
| | ISSUANCE WILL REQUIRE SEPARATE PERMITS. |