Plan Review Notes For Permit 05070365
Permit Number 05070365
Review Stop P
Sequence Number 1
Notes
Date Text
2007-04-30 14:02:07DENIED REVISION
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET 3 OF 4: CLEARLY INDICATE ON THE REVISION
 RESUBMITTAL IF THE BOOSTER PUMPS ARE FOR THE POTABLE
 WATER SYSTEM OR THE FIRE SYSTEM.
  
 2. PLEASE INDICATE ON THE RESUBMITTAL HOW THE BOOSTER
 PUMPS ARE ANCHORED TO MEET 140 MPH WIND LOADS PER
 FBC-2004 SECTION 1603.1.4 WIND DESIGN DATA AND SECTION
 1609.1.3 ANCHORAGE AGAINST OVERTURNING, UPLIFT AND
 SLIDING. (DETAIL REQUIRED)
  
 3. PER FBC-2004 PLUMBING, SECTION 606.5.5 LOW-PRESSURE
 CUTOFF REQUIRED ON BOOSTER PUMPS: A LOW-PRESSURE CUTOFF
 SHALL BE INSTALLED ON ALL BOOSTER PUMPS IN A WATER
 PRESSURE BOOSTER SYSTEM TO PREVENT THE CREATION OF A
 VACUUM OR NEGATIVE PRESSURE ON THE SUCTION SIDE OF THE
 PUMP WHEN A POSITIVE PRESSURE OF 10 PSI OR LESS OCCURS
 ON THE SUCTION SIDE OF THE PUMP. (PLEASE INDICATE A
 LOW-PRESSURE CUTOFF ON THE RESUBMITTED REVISION)
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  