| 2007-06-21 18:22:24 | BUILDING PLAN REVIEW |
| | PERMIT:05070334/ 03031228/ 01051303 |
| | ADD: 4011 NORTH SHORE DR. |
| | CONT: CARLO MERCURIO |
| | TEL: (561)329-8167 |
| | |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW: PLANS SUBMITTED BY ENGINEER ALONSO, ALFREDO |
| | C |
| | |
| | ACTION: DENIED |
| | 1 ) 110.2* W. P. B. ADMINISTRATIVE |
| | CODE, INFORMATION THAT IS REQUIRED FOR |
| | RECORD KEEPING & FOR CERTIFICATE OF |
| | OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH |
| | THE PROJECT WAS DESIGNED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. |
| | D) THE OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| | IS REQUIRED. |
| | F) ANY SPECIAL STIPULATIONS & CONDITIONS |
| | OF THE BUILDING PERMIT. |
| | G)SQ. FT. UNDER ROOF (TOTAL) |
| | H) FLOOD ZONE |
| | |
| | 2) FL ADMINISTRATIVE CODE 61G15-23.001(2) THE ENGINEER |
| | OF RECORD IS TO BE IN GOOD STANDING UNDER CHAPTER 471. |
| | SEE ATTACHMENT DEINGUENT LICENSE. |
| | |
| | 3)THE SEET OF PLANS ARE MISSING THE ARCHITECTURAL |
| | SHEETS PROVIDING THE LIFE SAFETY SHEETS, FLOOR LAYOUT, |
| | WALL RATINGS, DOOR RATINGS ,ETC. |
| | |
| | 4) SHEET S-17 IS MISSING THE GABLE WALL DETAIL, NOTE |
| | THAT THE MASONARY WALL IS TO CONTINUE TO THE GABLE TIE |
| | BEAM. |
| | |
| | 5) MEETING WITH THE NEIL MELICK THE BUILDING OFFICIAL |
| | THE REVIEWS WILL TAKE PLACE UNDER THE 2001 FBC. |
| | |
| | BUILDING PLAN REVIEW II |
| | JIM WITMER C. B. O. |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |