| 2007-06-26 17:09:23 | |
| | |
| | *** UNSAT *** |
| | |
| | REVISIONS: |
| | |
| | 1) NOTE: PLEASE SEE THE REVISIONS ARE NOW COMING IN |
| | DESIGNED AND SHOWING SEVERAL CODES WHICH ARE CURRENTLY |
| | IN EFFECT. PLEASE KNOW THE PERMITTED WORK FOR THIS |
| | BUILDING WAS UNDER PREVIOUS CODES AS STATED BELOW. |
| | ** PLEASE KNOW IF THE DESIGNS WERE UNDER THE 2004 FBC |
| | THERE WAS NO DESIGNS TO FBC CHAPTER 13. |
| | |
| | THE FOLLOWING CODES WERE APPLICABLE WHEN THIS PERMIT |
| | WAS APPLIED. |
| | 2001 FBC |
| | 1999 NFPA-70 (NEC). |
| | 1997 NFPA-101 LIFE SAFETY CODE |
| | 1999 NFPA-72 |
| | |
| | ** PLEASE SEE ANY COMMENTS FROM OTHER TRADE WHICH ALSO |
| | MAY REQUEST CERTAIN CODE CHANGES. |
| | |
| | 2) NOTE: NEW DESIGNERS OF RECORD: |
| | PLEASE SEE THE LICENSE NUMBER AS STATED AND SEALED ON |
| | PLANS IS SHOWN ON THE STATE WEBSITE FROM THE DEPARTMENT |
| | OF BUSINESS AND PROFESSIONAL REGULATION AS * |
| | DELINQUENT*. PLEASE SEE ATTACHED PRINT OUT FROM DBPR. |
| | FS 481. |
| | |
| | 3) NOTE: NEW ELECTRICAL DESIGNER/ENGINEER OF RECORD. |
| | PLEASE SEE THE SEAL WHICH IS BEING USED IS NO LONGER |
| | VALID WITH THE STATE OF FLORIDA. PLEASE SEE RULING |
| | UNDER THE FLORIDA ADMINISTRATIVE CODE 61G15-23.001 IN |
| | FEBRUARY 04 WHICH REQUIRED ALL SEALS FOR ENGINEERS TO |
| | CHANGE THE WORDING ON THE SEAL FROM *CERTIFICATE* TO |
| | THE WORDING OF *LICENSE*. AN EXTENSION WAS GIVEN TO THE |
| | DATE OF DECEMBER 31, 2005 HOWEVER ALL SEALED DOCUMENTS |
| | AFTER THAT DATE MUST HAVE NEW SEAL. PLEASE OBTAIN NEW |
| | SEAL FOR SAID DOCUMENTS. |
| | FS 471.025 |
| | |
| | 4) NOTE: PLEASE SEE MISSING INFORMATION FROM TITLE |
| | BLOCKS FOR ENGINEERING FIRM AS REQUIRED UNDER FAC |
| | 61G15-23.002 AND FLORIDA STATUTES 471.023. |
| | PLEASE SEE THE MISSING *CERTIFICATE OF AUTHORIZATION |
| | NUMBER* ALSO KNOWN AS THE ENGINEERING BUSINESS NUMBER |
| | OR FIRM LICENSE NUMBER. |
| | ** PLEASE SEE THIS IS REQUIRED FOR ALL SHEETS AND FOR |
| | ALL TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER |
| | TRADE(S). |
| | |
| | 5) NOTE: PLEASE SEE THE PLANS NEED TO SHOW ALL |
| | LOCATIONS AND ALL MINIMUM LEVELS FOR HORNS, STROBES AND |
| | HORN/STROBE DEVICES. |
| | PLEASE SEE 2001 FBC 11-4.28.1,.2, AND .3(4). |
| | |
| | 6) NOTE: PLEASE SUBMIT REVISED ENERGY CALCULATIONS PER |
| | 2001 FBC CHAPTER 13. |
| | A) PLEASE SEE THAT THESE ARE REQUIRED TO BE SIGNED, |
| | DATED, AND SEALED BY THE DESIGNER OF RECORD ALONG WITH |
| | SIGNATURE FROM OWNER AGENT. FS 481.221/ 471.025, FAC |
| | 61G15-23.002, 61G1-16.004 |
| | B) PLEASE SEE PLANS ARE MISSING THE FIXTURE LEGEND FOR |
| | LIGHTING FIXTURES. PLEASE PROVIDE ALL INFORMATION FOR |
| | THESE AND BE SURE TO CORRELATE WITH REVISED ENERGY |
| | CALCULATIONS. |
| | |
| | 7) NOTE: PLEASE SEE THE RISER DIAGRAM HAS NOW BEEN |
| | COMPLETELY REVISED WITH SEVERAL ITEMS INCLUDING NOW |
| | SHOWING A NEW SERVICE WHICH DOES NOT MEET THE |
| | EXCEPTIONS OF 230.2. |
| | PLEASE SEE THE RISER DIAGRAM ITSELF IS NOT SHOWN AS |
| | CODE COMPLIANT. |
| | PLEASE SEE THE SERVICE ENTRANCE CONDUCTORS ARE SHOWN |
| | FOR THE FPL TRANSFORMER UNDERGROUND AND THEN THERE ARE |
| | THREE SETS OF TAPS FROM THE SAME UNDERGROUND???? |
| | PLEASE SEE ONE TAP FOR A NEW A/C MAIN, A NEW FIRE PUMP |
| | MAIN, AND THE MAIN FOR THE BUILDING ELECTRICAL |
| | SERVICE. |
| | PLEASE SUBMIT A REVISED DIAGRAM WHICH INDICATES CODE |
| | COMPLIANCE WITH THE NEC. |
| | 215.5,240.21,230.2,230.70,230.71 ETC. |
| | THE TAPS AS SHOWN ON RISER ARE NOT CLEAR AND ARE NOT |
| | PERMITTED. |
| | |
| | 8) NOTE: PLEASE SEE RISER SHOWS AND NEW FIRE SPRINKLER |
| | MAIN WHICH CAN ONLY BE ASSUMED AS A FIRE PUMP MAINS |
| | HOWEVER THE PLANS DO NOT INDICATE ANY INFORMATION FOR |
| | THIS. |
| | PLEASE SEE 230.2, 230.70, 695.4 AND NFPA-20 FOR ALL |
| | INFORMATION NEEDED. |
| | PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS FOR THE |
| | FIRE PUMP AND FIRE PUMP CONTROLLER. |
| | PLEASE INDICATE THE LOCATION AND INFORMATION ON PLANS |
| | AS THESE COULD NOT BE LOCATED ON PLANS. |
| | ** PLEASE KNOW AS NO INFORMATION WAS SHOWN OR |
| | SUBMITTED, A REVIEW FOR CODE COMPLIANCE CAN NOT BE DONE |
| | AT THIS TIME. |
| | PLEASE SEE THE RISER AS SHOWN IS NOT CODE COMPLIANT. |
| | |
| | 9) NOTE: PLEASE SUBMIT THE AIC RATINGS FOR ALL SERVICE |
| | EQUIPMENT AS REQUIRED PER 110.9 OF THE NEC. |
| | |
| | 10) NOTE: PLEASE SEE THE TOTAL OF THE CONNECTED LOAD |
| | AMPS SEEMS TO BE A MISPRINT AS THIS SHOWS 110.5 AMPS. |
| | FBC104.1.2 COORDINATION. |
| | |
| | 11) NOTE: PLEASE SEE THE AIC RATING WHICH IS BEING |
| | SHOWN ON THE MDP AS 65K, JUST A NOTE AS EACH OF THE |
| | BRANCH BREAKERS IN THIS MLO WILL BE REQUIRED TO BE 65K |
| | RATED AS SHOWN. |
| | |
| | *** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |