| 2007-06-28 10:38:28 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. SHT P1 ONE SHEET ON ONE SET IS NOT SIGNED, SEALED, |
| | DATED AS REQUIRED BYSECTION 104.2.2, FAC |
| | 61G15-23.004(1)(2) & FS 471.025 |
| | |
| | 2. ALL ELECTRIC, MECHANICAL & PLUMBING SHEETS. THE |
| | CERTIFICATE OF AUTHORIZATION IS REQUIRED IN THE TITLE |
| | BLOCK OF THE ENGINEERING BUSINESS. FAC 61G15-23.002(2) |
| | & FS 471.025. |
| | |
| | 3. SHT P2 DELETE THE SANITARY BRANCH LINE DOWNSTREAM OF |
| | THE JANITOR SINK OR INDICATE THE USE FOR THIS LINE. |
| | (NOT SHOWN ON THE RISER DIAGRAM). SECTION 104.2.1. |
| | |
| | 4. SHT P3 A VENT IS REQUIRED FOR THE WATER CLOSET NEXT |
| | TO WATER HEATER 1A. TABLE 906.1. |
| | |
| | 5. SHT P4 DETAIL 1 SEE PREVIOUS COMMENT #4. |
| | |
| | 6. SHT P4 DETAIL 3 SEE COMMENT #3. |
| | |
| | 7. SHT P4 DETAIL 5 SHOW STUB-OUTS FOR THE URINALS. |
| | SECTION 104.2.1. |
| | |
| | 8. SHT P6 SANITARY RISER DIAGRAM DOES NOT REFLECT THE |
| | FLOOR PLAN. IN THE GIRLS TOILET ROOM AT THE LAVS, 4 |
| | W/C'S & FLOOR DRAIN, IN THE BOYS TOILET ROOM 1 URINAL |
| | IS MISSING. ALSO THE FLOOR PLAN IN THE BOYS SHOWER AT |
| | THE W/C AND THE GIRLS SHOWER THE W/C'S FACING EACH |
| | OTHER.--SINK-3, (NEXT TO W/H-3),IS MISSING |
| | BETWEEN TOILET ROOMS--THE WASTE ARMS FOR THE |
| | DRINKING FOUNTAINS AS INDICATED ARE "S" TRAPS AND SHALL |
| | STUB OUT STRAIGHT FROM THE FIXTURE BRANCH ARM.-- |
| | SINK-4'S SHALL NOT DRAIN THRU THE WET VENT OF THE |
| | TOILET ROOMS. SECTION 909.1 (THESE ARE LOCATED AT THE |
| | WEST SIDE OF THE FLOOR PLAN AND NEAR THE GREAS |
| | INTERCEPTOR).--INDICATE 2-WAY CLEANOUTS ON EACH |
| | SIDE OF THE GREASE INTERCEPTOR. --REMOVE ALL TRAPS AT |
| | THE WATER CLOSETS ON THE RISER DIAGRAM. THE WATER |
| | CLOSETS HAVE INTEGRAL TRAPS AND DOUBLE TRAPING IS NOT |
| | APPROVED. SECTIONS 104.2.1, 1002.1. (SEE RED LINE |
| | CORRECTIONS ON ONE SET OF PLANS). |
| | |
| | 9. SHT P8WATER HEATER DETAIL. SHOW THERMAL EXPANSION |
| | CONTROL AS REQUIRED IN SECTION 607.3.2.--FLOOR |
| | DRAINS ARE NOT APPROVED INDIRECT WASTE RECEPTORS. |
| | DELETE FROM DETAIL REFERENCE. SECTIONS 802.3 & 802.3.2. |
| | --DIELECTRIC UNIONS ARE NOT ANAPPROVED FITTING FOR |
| | USE IN THEWATER SYSTEM. CHANGE REFERENCE TO |
| | "COUPLING". |
| | |
| | 10. A LETTER INDICATING THAT AN ELECTRIC WATER HEATER |
| | HAS BEEN CHANGED TO A GAS WATER HEATER. A SEPARATE GAS |
| | PERMIT IS REQUIRED AND THE FOLLOWING INFORMATIO IS |
| | REQUIRED FOR THE GAS PERMIT: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | |
| | C. TYPE OF GAS, (LP OR NATURAL). |
| | |
| | D. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | |
| | F. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTION 304. |
| | |
| | G. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | |
| | H. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 505. |
| | |
| | I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | J. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | |
| | K. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| | PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | |
| | REVIEW BY KEN STEVENS |