 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PROVIDE A CALCULATION FOR THE LOAD
 INTENDED TO BE SERVED BY THE GENERATOR.
 SEE 702.5. LIGHTING LOADS MAY TAKE THE
 DEMAND FROM 220.3. ALL OTHERS AT 100%
 PER 702.5.
  
 2} INDICATE THE CONDUIT AND CONDUCTOR
 SIZE OF ALL BEING INSTALLED FOR THIS
 SYSTEM. SEE 445.13, FEEDER @ 115%
 NAMEPLATE.
  
 3} PLEASE SEE 225.30 THROUGH 225.37 FOR
 DISCONNECT RATING, GROUPING AND SIGNAGE
 REQUIREMENTS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  