| Plan Review Notes For Permit 05070322 |
| Permit Number |
05070322 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-01 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PROVIDE A CALCULATION FOR THE LOAD | | | INTENDED TO BE SERVED BY THE GENERATOR. | | | SEE 702.5. LIGHTING LOADS MAY TAKE THE | | | DEMAND FROM 220.3. ALL OTHERS AT 100% | | | PER 702.5. | | | | | | 2} INDICATE THE CONDUIT AND CONDUCTOR | | | SIZE OF ALL BEING INSTALLED FOR THIS | | | SYSTEM. SEE 445.13, FEEDER @ 115% | | | NAMEPLATE. | | | | | | 3} PLEASE SEE 225.30 THROUGH 225.37 FOR | | | DISCONNECT RATING, GROUPING AND SIGNAGE | | | REQUIREMENTS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|