| Plan Review Notes For Permit 05070318 |
| Permit Number |
05070318 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-27 00:00:00 | DENIED; | | | 1.PIPE SIZING NOT CORRECT. USE FBC FUEL | | | GAS TABLE 402(2). | | | 2.LONGEST RUN TO BE LISTED ON PLAN. | | | 3.PERSON WHO DREW PLAN IS REQUIRED TO | | | PRIN AND SIGN THEIR NAME ON DRAWING. | | | 4.WATER HEATER MAKE UP AIR TO COMPLY | | | WITH 304.3.1. | | | COPIES OF CODE INCLOSED. | | | GAS PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|