2007-04-03 13:56:05BUILDING PLAN REVIEW
 PERMIT: 05070317
 ADD: 6815 S FLAGLER
 CONT: HINCKLEY CONSTRUCTION
 TEL: (561)718-9051
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 * WEST PALM BEACH AMENDMENTS
  
 REVISION REVIEW
 ACTION: DENIED
  
 1)104.1.2* /2001 FBCADDITIONAL INFORMATION
 REQUIRED,
 PLEASE PROVIDE MANUFACTURERS SPECS FOR LOCATION OF UNIT
 NEXT TO
 STRUCTURES. THIS OFFICE INDICATES IN THE KOHLER SPECS
 THE GENERATOR
 PLACEMENT A MINIMUM OF 3'-0" FROM OTHER STRUCTURES.
 110.3 NEC
 90.7 NEC
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]