| 2005-08-13 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05070317 |
| | ADD: 6815 S FLAGLER DR |
| | CONT: HINKLEY CONSTRUCTION |
| | TEL: (561)718-9051 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) NO SURVEY SITE PLAN, NOTE! |
| | FL S S 472.025 / 61G17-6.002(8)(E) |
| | |
| | 61G17-6.002(8)(E) ALL SURVEY MAPS AND |
| | REPORTS OR COPIES THEREOF ARE NOT VALID |
| | WITHOUT THE ORIGINAL SIGNATURE, AND THE |
| | ORIGINAL RAISED SEAL OF A FLORIDA FOR |
| | LICENSED SURVEYORS AND MAPPERS. |
| | |
| | 61G17-6.002(8)(C) ALL SURVEY MAPS AND |
| | REPORTS MUST BEAR THE NAME, "CERTIFICATE |
| | OF AUTHORIZATION NUMBER", AND THE STREET |
| | MAILING ADDRESS OF THE BUSINESS ENITITY |
| | ISSUING THE MAP OR REPORT, ALONG WITH |
| | NAME AND LICENSE NUMBER OF THE SURVEYOR |
| | AND MAPPER IN RESPONSIBLE CHARGE. |
| | |
| | 2) GENERATOR SLAB & ANCHOR REQUIREMENT |
| | PLEASE PROVIDE SIZE OF GENERATOR(WXL), |
| | PLUS PROVIDE PLANS WITH THE INFORMATION |
| | DEPICTING HOLD DOWN BRACKETS, TYPE OF |
| | FASTENER, AND THE MINIMUM EDGE DISTANCE |
| | THE DEVICE REQUIRES WITHOUT LOAD |
| | REDUCTION. |
| | SECOND, PROVIDE INFORMATION ON THE |
| | SLAB, THICKNESS, WIDTH AND LENGTH, IF |
| | WIREMESH, FIBER MESH OR IF STEEL REBAR |
| | WILL BEUSED. |
| | THE NEW SLAB AND HOLD DOWN DETAILS: |
| | 104.2.1* ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA |
| | SHALL BEAR THE NAME AND SIGNATURE OF THE |
| | PERSON RESPONSIBLE FOR THE DESIGN. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |