| Plan Review Notes For Permit 05070295 |
| Permit Number |
05070295 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-04-12 00:00:00 | PLAN DENIED | | | 1) EQUIPMENT SCHEDULE SHOWS FIVE RTU | | | MECHANICAL PLANS SHOW SIX RTU. | | | 2) MISSING SUPLY DUCT IN THE OFFICE OFF | | | RTU #6. | | | 3) MISSING RETURN AIR DUCT SIZE OFF | | | RTU #6 | | | 4) PLEASE PROVIDE RETURN AIR DUCT AND | | | GRILL SIZE FOR OFFICE OFF RTU #1 | | | 5) PLEASE PROVIDE TWO COPYS OF ENERGY | | | CALCULATIONS WITH PLANS. | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 | | | |
|