| 2006-01-06 00:00:00 | ********** UNSAT *********** |
| | |
| | |
| | 1)NOTE: PLEASE KNOW, ELECTRICAL AND |
| | MECHANICAL AND PLUMBING PLANS ARE NOW |
| | COMING IN SIGNED,SEALED BY AN ARCHITECT. |
| | THIS IS ASSUMING THE WORK OF ANOTHER |
| | DESIGNER. PLEASE SEE THE ORIGINAL |
| | DESIGNER OF RECORD WHICH WAS AN ENGINEER |
| | IS STILL SHOWN ON PLANS AND ALSO |
| | CONTAINS A PHOTOCOPY OF THE ORIGINAL |
| | SIGNATURE AND SEALED BY SAID ENGINEER OF |
| | RECORD. |
| | PLEASE SEE FS 481.221 (5)(6) WHICH |
| | STATES: |
| | (5) NO REGISTERED INTERIOR DESIGNER |
| | SHALL AFFIX, OR PERMIT TO BE AFFIXED, |
| | HER OR HIS SEAL OR SIGNATURE TO ANY |
| | PLAN, SPECIFICATION, DRAWING, OR OTHER |
| | DOCUMENT WHICH DEPICTS WORK WHICH SHE OR |
| | HE IS NOT COMPETENT OR LICENSED TO |
| | PERFORM. |
| | |
| | (6)NO REGISTERED ARCHITECT SHALL AFFIX |
| | HER OR HIS SIGNATURE OR SEAL TO ANY |
| | FINAL CONSTRUCTION DOCUMENT OR |
| | INSTRUMENT OF SERVICE WHICH INCLUDES |
| | DRAWINGS, PLANS, SPECIFICATIONS, OR |
| | ARCHITECTURAL DOCUMENTS WHICH WERE NOT |
| | PREPARED BY HER OR HIM OR UNDER HER OR |
| | HIS RESPONSIBLE SUPERVISING CONTROL OR |
| | BY ANOTHER REGISTERED ARCHITECT AND |
| | REVIEWED, APPROVED, OR MODIFIED AND |
| | ADOPTED BY HER OR HIM AS HER OR HIS OWN |
| | WORK ACCORDING TO RULES ADOPTED BY THE |
| | BOARD. |
| | |
| | ** PLEASE KNOW THE ORIGINAL DESIGNER'S |
| | OF RECORD HAVE BEEN CONTACTED AND ONE |
| | COPY OF SAID PLANS ARE BEING RETAINED |
| | FOR FILE FOR REVIEW BY THE STATE BOARD |
| | OF ARCHITECT'S. |
| | THIS HAS BEEN CONFIRMED WITH THE |
| | BUILDING OFFICAL. |
| | IT WAS MENTIONED TO THE ELECTRICAL |
| | CONTRACTOR AND OWNER OF RECORD IN A |
| | MEETING BEFORE PLANS WERE RE-SUBMITTED |
| | THE PLANS NEEDED TO GO BACK TO THE |
| | ORIGINAL DESIGNER OF RECORD FOR CHNAGES |
| | TO PLANS AND BE SIGNED, DATED AND SEALED |
| | BY THAT DESIGNER. |
| | |
| | ********* |
| | PLEASE SEE THE FOLLOWING COMMENTS, SOME |
| | FROM PREVIOUS REVIEWS AND SOME FROM THIS |
| | REVIEW. |
| | |
| | 1)NOTE: PLEASE SEE ROOM/AREA |
| | DESIGNATIONS WERE ADDED TO PLANS, |
| | HOWEVER PLEASE SEE MAIN ELECTRICAL RM IS |
| | SHOWN AS "STOCKRM". PLEASE SEE |
| | 110.26,408.7, 240.24 ETC WHICH DOES NOT |
| | PERMIT STORAGE WITH THIS ELECTRICAL |
| | EQUIPMENT. |
| | |
| | 2)NOTE: PLEASE CORRELATE PANELS WITH |
| | RISER DIAGRAM, ONE SHOWS 125A AND OTHERS |
| | SHOW 100A. |
| | 215.5 |
| | PREVIOUS NOTES. |
| | |
| | 3)NOTE: PLEASE SEE RISER IS NOW SHOWING |
| | CONDUCTORS BEING INSTALLED TO THE |
| | "FUTURE" METERS AND MAINS? THESE WOULD |
| | NO LONGER BE "FUTURE". PLEASE ADJUST AND |
| | COMPLETE RISER ACCORDINGLY. |
| | |
| | 4)NOTE: PLEASE SEE KITCHEN/BREAK AREA |
| | SHALL HAVE GFI PROTECTION FOR ALL 15/20A |
| | 120V RECEPTS. |
| | |
| | 5)NOTE: PLEASE SEE FS 553.80(2)(B) WHICH |
| | IS STILL IN EFFECT. |
| | |
| | PLEASE SEE OTHER COMMENTS FROM OTHER |
| | REVIEWERS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICALPLAN REVIEW |