| 2005-09-10 00:00:00 | *********** UNSAT 2ND REVIEW ********** |
| | |
| | PLEASE SEE SOME COMMENTS FROM PREVIOUS |
| | REVIEW STILL NEED TO BE ADDRESSED. |
| | |
| | 1)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH PANEL SCHEDULES |
| | SUBMITTED. |
| | PLEASE SEE THERE ARE NUMEROUS CIRCUITS |
| | ON PLANS WHICH DO NOT CORRELATE. |
| | PLEASE SEE |
| | A-5 SHOWN AS SIGN CIR AND SHOWN AS |
| | RECEPTS ON PLANS. |
| | PLEASE SEE STORE AREA SHOWS CIRCUITS TO |
| | PANEL "A" FOR LIGHTING , HOWEVER PANEL |
| | "A" IF FOR A SEPRATE SPACE. |
| | PLEASE ALSO SEE 700.12E WHICH REQUIRES |
| | THE BRANCH CIRCUIT FEEDING THE UNIT |
| | EQUIPMENT SHALL BE THE SAME BRANCH |
| | CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD |
| | OF ANY LOCAL SWITCHES. |
| | PLEASE SE SOME CIRCUITS SHOWN ON PLANS, |
| | NOTHING IS SHOWN ON PANEL SCHEDULE. |
| | PLEASE SEE REDLINED PLANS FOR OTHER |
| | ITEMS. |
| | |
| | 2)NOTE: PLEASE SEE PLANS STILL MISSING |
| | ROOM/ AREA DESIGNATIONS ON PLANS. |
| | OFFICE/STORAGE, BATHS, KITCHENS ETC. |
| | |
| | 3)NOTE: PLEASE SEE 2002 NEC 210.8B3 |
| | WHICH REQUIRES ALL 15/20A 125V RECEPTS |
| | IN KTICHEN AREAS OFNON-DWELLING UNIT |
| | TO BE GFI/GFI PROTECTED. THIS IS |
| | REQUIRED WHETHER OR NOT RECEPT SERVES |
| | COUNTERSPACE. |
| | |
| | 4)NOTE: PLEASE SEE MIN VA FOR WINDOW |
| | LINEAR FT. 200 VA PER FT. SCALE SEEMS TO |
| | INDICATES 22' +/-. 220.12 |
| | |
| | 5)NOTE: PLEASE CORRELATE PANELS ON RISER |
| | WITH PANEL SCHEDULES. 100A/125A, |
| | 100A/125A?? |
| | 215.5 |
| | |
| | 6)NOTE: PLEASE INDICATE CONDUCTORS FROM |
| | GUTTER TO EACH NEW METER AND FROM METER |
| | TO MAINS. |
| | 215.5,215.3,240.4,310.16, ETC |
| | PLEASE BE SURE "EQUIPMENT GROUNDING |
| | CONDUCTORS" ARE ONLY INSTALLED AFTER THE |
| | FIRST MEANS OF DISCONNECT. 250.6 |
| | |
| | 7)NOTE: PLEASE SEE RISER INDICATES |
| | GROUNDING ELECTRODE TO FOOTER STEEL. ?? |
| | THIS SEEMS TO BE AN EXISTING BLDG AND |
| | FOOTER STEEL WOULD NOT BE REQUIRED TO AN |
| | EXISTING BLDG, HOWEVER MAY BE DONE. |
| | IF THIS IS SHOWN, THEN IT WILL BE |
| | REQUIRED. |
| | PLEASE SEE THAT 2-GRND RODS WILL BE |
| | REQUIRED. |
| | 250.50 |
| | |
| | |
| | 8)NOTE: PLEASE SEE COPY OF FS |
| | 553.80(2)(B) ATTACHED WITH RESPECT TO |
| | DESIGN PROFESSIONALS AND PLANS WITH |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. |
| | PLEASE SEE THIS IS ONLY A NOTICE GIVEN |
| | AT THIS TIME. |
| | |
| | |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE BE SURE TO SEE ANY COMMENTS FROM |
| | OTHER REVIEW(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |