| 2005-10-14 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT:05070295 |
| | ADD: 1256 PALM BEACH LAKES BLVD |
| | CONT: MASTER CONTRACTORS |
| | TEL: (561)712-8898 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PLANS NOW INDICATE A TRUE TENENT |
| | SEPERATION WALL. PROVIDE A 1HR RATED |
| | WALL ASSEMBLY (UL OR EQUIVALENT)TO THE |
| | METAL ROOF DECK.704.1.1. |
| | |
| | 2)PROVIDE THIS INFORMATION ON PLAN. |
| | 704.2.1.4 CORRIDOR PARTITIONS, SMOKESTOP |
| | PARTITIONS, HORIZONTAL EXIT PARTITIONS, |
| | EXIT ENCLOSURES, AND FIRE RATED WALLS |
| | REQUIRED TO HAVE PROTECTED OPENINGS |
| | SHALL BE EFFECTIVELY AND PERMANENTLY |
| | IDENTIFIED WITH SIGNS OR STENCILING IN A |
| | MANNER ACCEPTABLE TO THE AUTHORITY |
| | HAVING JURISDICTION.SUCH |
| | IDENTIFICATION SHALL BE ABOVE ANY |
| | DECORATIVE CEILING AND IN CONCEALED |
| | SPACES.SUGGESTED WORDING:FIRE AND |
| | SMOKE BARRIER PROTECT ALL OPENINGS. |
| | |
| | 3)ND ROOF DECK.(UL OR |
| | EQUIVALENT) PROVIDE A FLEXIBLE JOINT |
| | FIRE AND |
| | SMOKE ASSEMBLY AT THE TENANT SEPERATION |
| | BETWEEN WALL A |
| | 705.7.1 JOINTS INSTALLED IN OR BETWEEN |
| | FIRE RESISTANT WALLS, FIRE RESIS- TANT |
| | FLOORS OR FLOOR/ CEILING ASSEMBLIES AND |
| | FIRE RESISTANT ROOFS OR ROOF/ CEILING |
| | ASSEMBLIES SHALL BE PROTECTED BY AN |
| | APPROVED FIRE RESISTANT JOINT SYSTEM |
| | DESIGNED TO RESIST THE PASSAGE OF FIRE |
| | FOR A PERIOD NOT LESS THAN THE REQUIRED |
| | FIRE RESISTANCE RATING OF THE WALL, |
| | FLOOR OR FLOOR IN OR BETWEEN |
| | WHICH IT IS INSTALLED. |
| | |
| | 4) DISCREPANCY BETWEEN THE A-2 & THE |
| | MEP-1 SHEET THE NEW OFFICE DOORS ARE IN |
| | DIFFERENT WALLS, PLEASE CORRECT. |
| | |
| | 5) NEW OFFICE LOOKS LIKE THERE IS A |
| | KITCHEN AREA, IF SO COMPLY WITH: |
| | 11-4.24.2 SINKS, HEIGHT. SINKS SHALL |
| | BE MOUNTED WITH THE COUNTER NO HIGHER |
| | THAN 34" ABOVE THE FINISH FLOOR. |
| | 11-4.24.3 KNEE CLEARENCE THAT IS AT |
| | LEAST 27" HIGH 30" WIDE, AND 19" DEEP |
| | SHALL BE PROVIDED UNDERNEATH SINKS. |
| | |
| | 6A) PRODUCT APPROVALS, THE ARCH EXTERIOR |
| | DOORS AND PANEL WALL SYSTEMS SUBMITTED |
| | WILL REQUIREA HURRICANE PROTECTIVE |
| | SYSTEM. PROVIDE PRODUCT APPROVAL REPORT |
| | FOR STORM SHUTTERS WITH A FL COVER |
| | SHEET. |
| | PROVIDE STORM PANEL INFORMATION WITH |
| | INSTALLATION SCHEDULE AND KEY PLAN WITH |
| | SPECIFIC ANCHORS AND MOUNTING TO BE USED |
| | FOR ALL NON-IMPACT GLAZING. |
| | FBC 1606.1.4. |
| | FL BLD CODE 2001 SECTION 103.6, |
| | 1606.1.4, 1707.4 & 3401.7.2.4. |
| | PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| | SCHEDULE SUMMARIZING & IDENTIFYING |
| | OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| | BAR REINFORCING REQUIREMENTS, WALL PRES- |
| | SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| | SUBMITTED AT TIME OF PERMIT APPLICATION |
| | TO FACILITATE PLAN REVIEW AND PERMIT |
| | ISSUANCE. |
| | 6B) FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | THE DOOR SCHEDULE INDICATES DOOR# 3 TO |
| | BE A HOLLOW CORE METAL CLAD DOOR, WHERE |
| | AS THE FLOOR PLAN & ELEVATIONS INDICATE |
| | GLASS DOORS WITH SIDE LIGHTS. |
| | 6C) 2405.2.1 THE FOLLOWING SHALL BE |
| | CONSIDERED SPECIFIC HAZARDOUS LOCATIONS |
| | FOR THE PURPOSES OF GLAZING: |
| | |
| | 1. GLAZING IN SWINGING DOORS AND |
| | FIXED AND SLIDING PANELS OF SLIDING |
| | (PATIO) DOOR ASSEMBLIES. |
| | |
| | 2. GLAZING IN DOORS AND WALLS OF |
| | ENCLOSURES FOR HOT TUBS, WHIRLPOOLS, |
| | SAUNAS, STEAM ROOMS, BATHTUBS, |
| | SHOWERS AND OTHER SUCH FACILITIES |
| | WHERE SUCH GLAZING IS LOCATED 36 |
| | INCHES (914 MM) OR LESS, MEASURED |
| | HORIZONTALLY, FROM A STANDING OR |
| | WALKING SURFACE WITHIN THE ENCLOSURE |
| | AND WHERE THE BOTTOM EDGE OF THE |
| | EXPOSED GLAZING IS LESS THAN 60 |
| | INCHES (1524 MM), MEASURED |
| | VERTICALLY, ABOVE SUCH STANDING OR |
| | WALKING |
| | SURFACES. |
| | |
| | 3. GLAZING IN AN INDIVIDUAL FIXED OR |
| | OPERABLE PANEL ADJACENT TO A DOOR |
| | WHERE THE NEAREST VERTICAL EDGE |
| | IS WITHIN A 24-INCH (610 MM) RADIUS |
| | OF THE DOOR IN A CLOSED POSITION |
| | AND WHOSE BOTTOM EDGE IS LESS THAN |
| | 60 INCHES (1524 MM) ABOVE THE |
| | FLOOR OR WALKING SURFACE. |
| | |
| | |
| | |
| | 7)BEFORE THIS PERMIT IS ISSUED,TO |
| | PERMITS HAVE TO BE ISSUED, SEE |
| | ATTACHMENTS: |
| | 7A) INTERIOR DEMO PERMIT |
| | 7B) EXTERIOR STUCCO |
| | IN BOTH CASES THE WORK HAS BEEN |
| | COMPLETED WITHOUT THE BENIFET OF A |
| | PERMIT!!!!!!!! |
| | |
| | 8) PLANS INDICATE EXISTING HANDICAPPED |
| | RAMP PROVIDE HEIGHT OF THE EXISSTING |
| | RAMP AND CONFIGURATION. MAY REQUIRE |
| | UPGRADES, SEE 11-4.8 SLOPE, RISE, |
| | LANDINGS AND HANDRAILS. |
| | 11-4.8.8 OUTDOOR CONDITIONS. OUTDOOR |
| | RAMPS AND THEIR APPROACHES SHALL |
| | BE DESIGNED SO THAT WATER WILL NOT |
| | ACCUMULATE ON WALKING SURFACES. |
| | NOTE: |
| | 11-4.1.6(2) DUTY TO PROVIDE AN |
| | ACCESSIBLE PATH OF TRAVEL TO ALTERED |
| | AREAS SHALL BE DEEMED DISPROPORTIONATE |
| | TO THE OVERALL ALTERATION WHEN THE COST |
| | EXCEEDS 20 % OF THE COST OF THE ALTERA- |
| | TION TO THE PRIMARY FUNCTION AREA. |
| | (A)(I) AN ACCESSIBLE ENTRANCE |
| | (II) AN ACCESSIBLE ROUTE |
| | (III) AT LEAST ONE ACCESSIBLE REST- |
| | ROOM FOR EACH SEX OR A SINGLE |
| | UNISEX RESTROOM |
| | (IIII) ACCESSIBLE TELEPHONE |
| | (IV) ELEMENTS SUCH AS PARKING, STOR- |
| | AGE OR ALARMS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |