| 2005-07-30 00:00:00 | PAUL SCHMITZ, PLUMBING & GAS |
| | PLANS EXAMINER |
| | |
| | 561-805-6692 |
| | [email protected] |
| | PLUMBING PLAN REVIEW FBC 2001 DENIED |
| | (1) |
| | 1503.4 ROOF DRAINAGE. UNLESS ROOFS ARE |
| | SLOPED TO DRAIN OVER ROOF EDGES, |
| | ROOF DRAINS SHALL BE INSTALLED AT EACH |
| | LOW POINT OF THE ROOF.WHERE |
| | REQUIRED FOR ROOF DRAINAGE, SCUPPERS |
| | SHALL BE PLACED LEVEL WITH THE ROOF |
| | SURFACE IN A WALL OR PARAPET.THE |
| | SCUPPER SHALL BE LOCATED AS DETERMINED |
| | BY THE ROOF SLOPE AND CONTRIBUTING ROOF |
| | AREA. |
| | (2)?1503.4.2 OVERFLOW DRAINS AND |
| | SCUPPERS. WHERE ROOF DRAINS ARE |
| | REQUIRED, |
| | OVERFLOW DRAINS HAVING THE SAME SIZE |
| | AS THE ROOF DRAINS SHALL BE INSTALLED |
| | WITH THE INLET FLOW LINE LOCATED 2 |
| | INCHES (51 MM) ABOVE THE LOW POINT OF |
| | THE ROOF, OR OVERFLOW SCUPPERS SHALL |
| | BE A MINIMUM OF 4 INCHES (102 MM) IN |
| | HEIGHT AND SHALL BE PLACED IN WALLS OR |
| | PARAPETS WITH THE INLET FLOW LINE |
| | NOT LESS THAN 2 INCHES (51 MM) ABOVE |
| | THE ROOF SURFACE, EXCLUDING SUMPS, OR |
| | MORE THAN 4 INCHES (102 MM) ABOVE THE |
| | ROOF SURFACE AND SHALL BE LOCATED AS |
| | CLOSE AS PRACTICAL TO REQUIRED |
| | VERTICAL LEADERS OR DOWNSPOUTS OR WALL |
| | ANDPARAPET SCUPPERS.OVERFLOW DRAINS |
| | AND SCUPPERS SHALL ALSO COMPLY WITH THE |
| | FLORIDA BUILDING CODE, PLUMBING. |
| | (3)?1503.4.3 SIZING AND DISCHARGE. |
| | ROOF DRAINS, GUTTERS, SCUPPERS AND |
| | LEADERS SHALL BE SIZED AND DISCHARGED |
| | IN ACCORDANCE WITH THE FLORIDA |
| | BUILDING CODE, PLUMBING SEC 1106. |
| | (4)SHT A-2 FLOOR PLAN, DOES NOT MATCH |
| | SHT MEP-4, PLUMBING FIXTURE LOCATION. |
| | (5) SHT MEP-4 BACK TO BACK H/C REST RMS. |
| | DOORS NOT PERMITTED TO SWING IN TO CLEAR |
| | FLOOR SPACE, SEE FIG 30E FBC 2001 CH-11 |
| | (5)SHT MEP-4, BREAK ROOM SINK: |
| | SINKS REQUIRED TO BE ACCESSIBLE |
| | SEC 11-4.24.2HEIGHT 34" FF |
| | SEC 11-4.24.5 CLEAR FLOOR SPACE: |
| | 30" BY 48" |
| | SEC 11-24.24.4 SINK DEPTH: 6 1/2" MAX |
| | SEC 11-24.24.7 FAUCETS: LEVER TYPE. |
| | (6) BACK FLOW PREVENTERS REQUIRED, |
| | LOCAL ORDINANCE # 2853-95 |
| | END OF COMMENTS. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |