| 2005-07-25 00:00:00 | ************* UNSAT *************** |
| | |
| | 1)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH PANEL SCHEDULES |
| | SUBMITTED. |
| | 215.5 |
| | PLEASE BES URE TO SEE 700.12E FOR |
| | CIRCUITING OF EM.EXT LTS. |
| | |
| | 2)NOTE: PLEASE CORRELATE RISER DIAGRAM |
| | WITH PANELS SUBMITTED. 400A? 150A? |
| | 215.5 |
| | |
| | 3)NOTE: PLEASE SEE 240.4,310.16 FOR MIN |
| | SIZE OF FEEDERS TO PANEL "L" WHICH IS |
| | SHOWN BEING FED FROM 400A OCP. |
| | PLEASE SEE OTHER TWO FEEDERS TO SUB |
| | PANELS INDICATE #3 MCM? PLEASE SEE AWG |
| | FOR SIZES AND DISCRIPTION OF CONDUCTORS. |
| | THERE IS NO #3 MCM. |
| | |
| | 4)NOTE: PLEASE SEE 250.122 FOR SIZING OF |
| | EQUIPMENT GROUNDING CONDUCTORS. |
| | PLEASE SEE MAIN TO PANEL "L". |
| | |
| | 5)NOTE: PLEASE SEE PLANS SHALL BE |
| | SIGNED, DATED AND SEALED BY THE ENGINEER |
| | RESPONSIBLE FOR DESIGN. |
| | FS 471.025 |
| | |
| | 6)NOTE: PLEASE SEE MISSING INFORMATION |
| | REQUIRED IN TITLE BLOCK FOR ARCHITECT. |
| | PLEASE SEE SEAL SHALL BE CLEAR AND |
| | VISABLE AS REQUIRED UNDER FS 481.221. |
| | PLEASE SEE FAC 61G1-16.004 FOR MISSING |
| | INFORMATION. |
| | |
| | 7)NOTE: PLEASE CLARIFY IF SERVICE SHOWN |
| | IS NEW OR EXSITNG?? |
| | PLEASE SEE ONE MAIN IS SHOWN FOR |
| | "FUTURE", HOWEVER PANEL IS BEING SHOWN |
| | AS NEW AT THIS TIME. HOW IS THIS PANEL |
| | FED IF MAIN/ METER IS "FUTURE" |
| | |
| | 8)NOTE: PLEASE SEE 250.66 FIR MIN |
| | GROUNDING ELECTRODE CONDUCTOR. |
| | 2/0MIN. |
| | |
| | 9)NOTE: PLEASE SHOW ALLELECTRICAL |
| | EQUIPMENT ON PLANS. ALL MAINS, PANELS |
| | NEED TO BE SHOWN AT LOCATIONS ON PLANS. |
| | 215.5 |
| | |
| | 10)NOTE: PLEASE SEE AREAS ON PLANS WHERE |
| | NO ELECTRICAL IS SHOWN? LTS? |
| | |
| | 11)NOTE: PLEASE SHOW ALL ROOM/AREA |
| | DESIGNATIONS ON PLANS. |
| | |
| | 12)NOTE: PLEASE SEE 210.62,220.12 FOR |
| | MIN "SHOW ROOM" WINDOW RECEPTS REQUIRED. |
| | |
| | 13)NOTE: PLEASE SEE SOME ITEMS LISTED ON |
| | PANEL SCHEDULE, HOWEVER THESE ITEMS |
| | COULD NOT BE LCOATED ON PLANS? |
| | PARKING LTO LTS, IRRIGATION PUMP ETC.?? |
| | |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | PLEASE SUBMIT ONE COPY OF ALL OLD/VOIDED |
| | SHEETS FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELETCRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |