2005-07-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. INDICATE THE SUITE NUMBER ON THE
 APPLICATION PERMIT FOR PUBLIC RECORD AND
 TO LET INSPECTORS KNOW WHERE TO LOCATE
 THE WORK TO BE INSPECTED.
 2. SUBMIT A DETAIL FOR THE TOILET ROOM
 SHOWING COMPLIANCE WITH SECTIONS 11-4.16
 11-4.19, AND 11-4.22 AND ALL
 SUBSECTIONS.
 3. SUBMIT A DETAIL FOR THE KITCHEN SINK
 SHOWING COMPLIANCE WITH SECTION 11-4.24
 AND ALL SUBSECTIONS.
 4. SHT M.1 SANT. ISOMETRIC, ONLY THE
 FIXTURES WITHIN THE BATHROOM GROUP SHALL
 CONNECT TO THE WET-VENTED HORIZONTAL
 BRANCH DRAIN. ANY ADDITIONAL FIXTURES
 SHALL DISCHARGE DOWNSTREAM OF THE WET
 VENT. SECTION 909.1. KITCHEN SINK SHALL
 CONNECT DOWNSTREAM OF THE BATHROOM
 FIXTURES.
 5. INDICATE HOW THE CONDENSATE WILL BE
 DISCHARGE OUT OF THE BUILDING. SECTION
 104.2.1.
 6. ALL ARCHITECTURAL SHEETS, THE PRINTED
 NAME OF THE PERSON SEALING THE DOCUMENTS
 IS REQUIRED IN THE TITLE BLOCK. FAC
 61G1-16.004(6) AND FS 481.2055.
  