| Plan Review Notes For Permit 05070282 |
| Permit Number |
05070282 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-09 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. INDICATE THE SUITE NUMBER ON THE | | | APPLICATION PERMIT FOR PUBLIC RECORD AND | | | TO LET INSPECTORS KNOW WHERE TO LOCATE | | | THE WORK TO BE INSPECTED. | | | 2. SUBMIT A DETAIL FOR THE TOILET ROOM | | | SHOWING COMPLIANCE WITH SECTIONS 11-4.16 | | | 11-4.19, AND 11-4.22 AND ALL | | | SUBSECTIONS. | | | 3. SUBMIT A DETAIL FOR THE KITCHEN SINK | | | SHOWING COMPLIANCE WITH SECTION 11-4.24 | | | AND ALL SUBSECTIONS. | | | 4. SHT M.1 SANT. ISOMETRIC, ONLY THE | | | FIXTURES WITHIN THE BATHROOM GROUP SHALL | | | CONNECT TO THE WET-VENTED HORIZONTAL | | | BRANCH DRAIN. ANY ADDITIONAL FIXTURES | | | SHALL DISCHARGE DOWNSTREAM OF THE WET | | | VENT. SECTION 909.1. KITCHEN SINK SHALL | | | CONNECT DOWNSTREAM OF THE BATHROOM | | | FIXTURES. | | | 5. INDICATE HOW THE CONDENSATE WILL BE | | | DISCHARGE OUT OF THE BUILDING. SECTION | | | 104.2.1. | | | 6. ALL ARCHITECTURAL SHEETS, THE PRINTED | | | NAME OF THE PERSON SEALING THE DOCUMENTS | | | IS REQUIRED IN THE TITLE BLOCK. FAC | | | 61G1-16.004(6) AND FS 481.2055. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|