2005-07-12 00:00:00DENIED:
 1.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS IN ACCORDANCE WITH 2001
 FBC(M) TABLE 403.3.
  
 2.INDICATE OUTSIDE AIR DUCT SIZE,
 MATERIAL AND LAYOUT.
  
 3.FAN SHUTDOWN BY DUCT SMOKE DETECTORS
 WITH NOTIFICATION FOR SYSTEMS WITH A
 DESIGN CAPACITY GREATER THAN 2,000 CFM.
  