| Notes |
| Date |
Text |
| 2005-07-12 00:00:00 | DENIED: | | | 1.PLEASE PROVIDE OUTSIDE AIR | | | CALCULATIONS IN ACCORDANCE WITH 2001 | | | FBC(M) TABLE 403.3. | | | | | | 2.INDICATE OUTSIDE AIR DUCT SIZE, | | | MATERIAL AND LAYOUT. | | | | | | 3.FAN SHUTDOWN BY DUCT SMOKE DETECTORS | | | WITH NOTIFICATION FOR SYSTEMS WITH A | | | DESIGN CAPACITY GREATER THAN 2,000 CFM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|