| Plan Review Notes For Permit 05070282 |
| Permit Number |
05070282 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-11 00:00:00 | 1. DEMOLITION, RENOVATION, AND | | | CONSTRUCTION TO COMPLY WITH NFPA 241. | | | | | | 2. COULD NOT LOCATE ANY FIRE ALARM | | | EQUIPMENT IN NEW SPACE. PLEASE | | | ADVISE. | | | | | | 3. INTERIOR FINSIH CLASSIFICATION | | | SHALL COMPLY WITH APPLICABLE BUILDING | | | AND FIRE CODE REQUIREMENTS. | | | | | | 4. PORTABLE FIRE EXTINGUISHERS WILL BE | | | REQUIRED. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | 835-2910 |
|