Plan Review Notes
Plan Review Notes For Permit 05070282
Permit Number 05070282
Review Stop E
Sequence Number 1
Notes
Date Text
2005-07-12 00:00:00********** UNSAT ***********
  
 1)NOTE: PLEASE SEE SUITE/UNIT # SHALL BE
 ON PLANS AND STATED ON PERMIT
 APPLICATION.
 PLEASE SEE OTHER REVIEWER(S) COMMENTS
 ALSO.
  
 2)NOTE: PLEASE SEE FAC 61G1-16.004 FOR
 REQUIRED INFORMATION ON ARCHITECTUAL'S
 TITLE BLOCK. THIS IS NOT FOR ENGINEERING
 FIRM, HOWEVER ALL SHEETS WOULD BE
 AFFECTED.
  
 3)NOTE: PLEASE SEE KITCHENS AND BATHS
 ARE NOTED ON ARCHITECTUAL SHEETS AS
 BEING DISPLAY ONLY, HOWEVER ALL
 ELECTRICAL IS BEING SHOWN ON E-SHEETS.
 IF THESE ELECTRICAL DEVICES ARE GOING TO
 BE INSTALLED, PLEASE SEE THE FOLLOWING
 COMMENTS FOR CODE COMPLIANCE.
  
 A)NOTE: PLEASE SEE 2002 NEC 210.8B3
 WHICH REQUIRES ALL 15- AND 20-AMPERE,
 125-VOLT RECEPTACLES IN NONDWELLING-TYPE
 KITCHENS TO BE GFCI PROTECTED. THIS
 REQUIREMENT APPLIES TO EACH AND EVERY
 15- AND 20-AMPERE, 125-VOLT KITCHEN
 RECEPTACLE, WHETHER OR NOT THE
 RECEPTACLE SERVES COUNTERTOP APPLIANCES.
  
 B)NOTE: PLEASE SEE GFI LOCATION IN BATH
 RM SHALL BE LOCATED WITH-IN 3' OF SINK
 EGDE, BY EITHER ADDTION OF SECOND RECEPT
 OR MOVING SHOWN GFI TO CENTER OF BOTH
 LAV'S.
 210.52D
  
 C)NOTE: PLEASE SEE GFI RECEPT BEING
 SHOWN FOR WHAT APPEARS TO BE A JACUZZI
 TUB? IF INDDED A JACUZZI TUB WILL BE
 INSTALLEDWITH MOTR, PLEASE VERIFY LOAD
 AND CIRCUITING. PLEASE SEE THIS CIRCUIT
 IS SHOWN FEEDING MANY OTHER RECEPTS
 INCLUDING ALL RECEPTS IN COPY RM?
 215.5
  
 4)NOTE: PLEASE VERIFY NEW OR EXSITNG
 SIGN CIRCUIT WHICH WILL BE REQUIRED.
 600.5
  
 5)NOTE: PLEASE INDICATE THE METHOD OF
 EQUIPMENT GROUNDING FROM MAIN DISCONNECT
 TO PANEL. 250.110,250.24, 250.122
  
 6)NOTE: PLEASE VERIFY AND SHOW LOAD ON
 EXISTING SERVICE WITH NEW ADDED LOADS.
 PLEASE VERIFY / SHOW EXISTING SEC'S
 215.5, 220
  
 PLEASE SEE OTHER POSSIBLE NOTES FORM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT ON SET/COPY OF OLD/VOIDED
 SHEETS FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved