| 2005-09-10 00:00:00 | *********** UNSAT *************** |
| | |
| | |
| | 1)NOTE: PLEASE CORRELAT ALL ELECTRICAL |
| | AND PLUMB PLANS SUBMITTED. |
| | PLEASE SEE PLUMB PLANS SHOWS NEW 5HP |
| | PUMPS FOR FOUNTAINS AND ELECTRICAL SHOWS |
| | 2- 2HP PUMPS?? |
| | PLEASE SEE THE FOLLOWING COMMENTS. |
| | |
| | 2)NOTE: PLEASE SEE PANEL SCHEDULE FOR |
| | EXISTING 200A PANEL DOES NOT INCLUDE ANY |
| | OCP , CONDUIT OR FEEDER SIZES TO NEW |
| | PANEL.? |
| | 240.4,310.16, ETC. |
| | PLEASE ALSO SEE THIS PANEL SHOWS 2-P20A |
| | BRKR FEEDING 5HP PUMP. |
| | PLEASE SEE NEC MIN OCP, AWG 430.148. |
| | |
| | 3)NOTE: PLEASE SEE PANEL SCHEDULE SHOWS |
| | PANEL AS EXISTING , YET RISER SHOWS THIS |
| | PANEL AS BEING NEW? PLEASE CORRELATE. |
| | |
| | 4)NOTE: PLEASE SIZE OVERCURRENT |
| | PROTECTION, CONDUCTOR SIZES ETC FOR |
| | ??WHICH SIZE PUMPS WILL BE INSTALLED. |
| | |
| | 5)NOTE: PLEASE SEE CONTINUOUS LOADS ARE |
| | SHOWN AS 125% FOR BOTH PUMPS OR ANY |
| | LOADS, 3 OR MORE HRS. PLEASE SEE THE |
| | ADDITIONAL 125% IS THEN FIGURED ABOVE |
| | FOR LARGEST MOTOR. |
| | PANEL SCHEDULE ONLY SHOWS CONTINUOUS |
| | LOAD FOR ONE MOTOR. |
| | 215.3,230.42 ETC. |
| | |
| | 6)NOTE: PLEASE SEE ONLY ONE TIME CLOCK |
| | IS SHOWN FOR BOTH MOTORS, THIS MAY |
| | CHANGE ONCE PUMP SIZE CORRELATES AND IS |
| | DETERMINED. |
| | IF 5HP, ONE TCV WILL NOT BE LARGE ENOUGH |
| | FOR BOTH, UNLESS THIS FEEDE STARTER |
| | CONTACTORS. |
| | THIS IS ONLY A NOTE , AS COORDINATION |
| | ISSUES STILL NED TO BE ADDRESSED. |
| | |
| | 7)NOTE: PLEASE SEE COPY OF FS |
| | 553.80(2)(B) IS NOW ATTACHED WITH |
| | RESPECT TO DESIGN PROFESSIONAL AND PLANS |
| | WITH REPEAT COMMENTS. |
| | THIS IS ONLY A NOTICE GIVEN AT THIS |
| | TIME. |
| | |
| | 8)NOTE: PLEASE SEE THAT 2-GRND RODS WILL |
| | BE REQUIRED. 250.50,250.56 |
| | |
| | 9)NOTE: PLEASE SEE NEW GFI IS INDICATED |
| | ON PANEL SCHEDULE, HOWEVER THIS IS NOT |
| | SHOWN ON PLANS.? |
| | |
| | LTR FOR ARCHITECT'S LEGAL SIGNATURE |
| | RECEIVED AND PLACED IN SIG. FILE. |
| | |
| | PLEASE REMOVE ANY OLD/VOIDED SHEETS FROM |
| | SETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO COMPLETED SETS FOR REVIEW AND |
| | STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |