| 2005-07-20 00:00:00 | ***********UNSAT ************ |
| | |
| | 1)NOTE: PELASE CORRELATE RISER DIAGRAM |
| | WITH PANEL "A". PLEASE SEE PANEL "A" IS |
| | SHOWN AS 200A MLO AND RISER SHOWS THIS |
| | AS 225A MCB. |
| | 215.5 |
| | |
| | 2)NOTE: PLEASE SEE SD IN MASTER BEDRM |
| | NEEDS TO BE MOVED INTOBEDROOM AREA. |
| | NFPA-72 8-1.4.1.6.2 |
| | |
| | |
| | 3)NOTE: PLEASE SEE PLANS INDICATE TWO |
| | GARAGE DOOR OPENERS, HOWEVER ONLY ONE |
| | CIRCUIT IS SHOWN ON PANEL SCHEDULE FOR |
| | THESE. |
| | PLEASE SEE ANY MOTOR LOADS 430.53 WHICH |
| | MAY REQUIRE A DEDICATED CIRCUIT FOR |
| | EACH. PLEASE VERIFY HP RATING OF GDO'S. |
| | |
| | 4)NOTE: PLEASE SEE SMOKE DETECTORS ARE |
| | SHOWN CIRCUITED TO A-20, HOWEVER THIS |
| | SPACE IS SHOWN AS SPARE IN PANEL? |
| | PLEASE ALSO SEE 210.12 OF THE 2002 NEC. |
| | |
| | 5)NOTE: PLEASE SEE WHIRLPOOL TUB ON |
| | PANEL SCHEDULE SHOWS GFI PROTECTION AS |
| | OPTIONAL. PLEASE SEE 680.71, GFI IS |
| | REQUUIRED. |
| | |
| | 6)NOTE: PLEASE HAVE ARCHITECT PROVIDE A |
| | SIGNED, DATED AND SEALED NOTORIZED LTR |
| | TO VERIFY SIGNATURE ON PLANS IS INDEED |
| | HIS LEGAL SIGNATURE. |
| | LTR SHOULD BE PROPERLY NOTORIZED UNDER |
| | FS 117 |
| | THIS SHALL BE PLACED IN SIGNATURE FILE |
| | FOR REFERENCE ONLY. |
| | |
| | PLEASE REMOVE ANY OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONCE COPY OF OLD SHEETS SHOUDL BE |
| | SUBMITTED FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW , IF THERE ARE ANY QUESTIONS, |
| | PLEASEDO NOT HESITATE TO CALL. |
| | |