| Plan Review Notes For Permit 05070240 |
| Permit Number |
05070240 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-05 00:00:00 | BUILDING REVIEW PROVISO: | | | 1- SHUTTERS UNDER A SEPARATE PERMIT. | | | 2- PROVIDE COMPLETE SHOP DRAWINGS FOR | | | STAIRCASE CONSTRUCTION. ARCHITECT TO | | | REVIEW THEM PRIOR TO SUBMITTAL. | | | 3- REVISE FRONT ELEVATION. SEE ENTRY | | | DOOR W/ SIDELITE PRODUCT APPROVAL. | | | REMEMBER THAT DOOR IS USED FOR EMERGENCY | | | EGRESS REQUIRED BY 1005.4.5 FBC 2001. | | | NEED IMPACT GLASS OR SOLID DOOR. | | | 4- PROVIDE PRODUCT APPROVAL FOR: | | | A) ENTRY DOOR WITH SIDELITE. SEE PLANS. | | | B) FIXED WINDOWS. NEED FLORIDA APPROVAL | | | C) ROOF TILE. NEED FLORIA PRODUCT | | | APPROVAL THAT MATCHES NOA SUBMITTED. | | | D) SINGLE HUNG WINDOWS.NEED FL APPROVAL. | | | 5- SOIL TEST REPORT RECOMMENDS 18" | | | FOOTERS. PLANS CALL FOR 16" FOOTERS. | | | REVISE EITHER ONE TO MATCH. |
|