| Plan Review Notes For Permit 05070224 |
| Permit Number |
05070224 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-11-12 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | | | | 1. BOTH SETS OF MECHINCAL AND ELECTRICAL | | | SHEETS SHALL BE SIGNED, SEALED, AND | | | DATED PER FAC 61G15-23.002(1) & FS | | | 471.2055. - STILL SHEET NOT SIGNED, | | | SEALED, DATED | | | 2. SHT A-1 SHOWS A KITCHEN SINK, AND | | | SINCE THERE IS NO DEMO SHEET, EXISTING | | | FLOOR PLAN, OR NOT INDICATED AS AN | | | EXISTING SINK, THE SINK SHALL BE | | | ACCESSIBLE. PLEASE SUBMIT A DETAIL | | | SHOWING COMPLIANCE WITH SECTION 11-4.24 | | | AND ALL SUBSECTIONS. - NO RESPONSE NOTED | | | TO THIS COMMENT. - FORWARD APPROACH | | | REQUIRED WITH NO CABINET DOORS ALLOWDED. | | | ALSO DOOR CAN NOT SWING INTO CLEAR FLOOR | | | SPACE OF ANY FIXTURE. | | | 3. SUBMIT A SANT. AND A WATER RISER | | | DIAGRAM IN ISOMETRIC FORM. SHOW ALL PIPE | | | SIZES, TRAP, VENT/SANT CONNECTIONS FOR | | | THE SANT. AND SHOW ALL PIPE SIZES, | | | VALVES, WATER HAMMER ARRESTORS, (IF | | | REQUIRED BY SECTION 604.9), AND POINT OF | | | CONNECTION. SECTION 104.3.1.1. - NO | | | RESPONSE TO COMMENT. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|