Plan Review Notes For Permit 05070224
Permit Number 05070224
Review Stop P
Sequence Number 1
Notes
Date Text
2005-08-08 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL ARCHITECTURAL SHEETS: PER FAC
 61G1-16.004(2) & FS 481.219 THE FIRM
 LICENSE NUMBER, (CERTIFICATE OF
 AUTHORIZATION), IS REQUIRED IN THE TITLE
 BLOCK OF EACH SHEET.
 2. BOTH SETS OF MECHINCAL AND ELECTRICAL
 SHEETS SHALL BE SIGNED, SEALED, AND
 DATED PER FAC 61G15-23.002(1) & FS
 471.2055.
 3. SHT A-1 SHOWS A KITCHEN SINK, AND
 SINCE THERE IS NO DEMO SHEET, EXISTING
 FLOOR PLAN, OR NOT INDICATED AS AN
 EXISTING SINK, THE SINK SHALL BE
 ACCESSIBLE. PLEASE SUBMIT A DETAIL
 SHOWING COMPLIANCE WITH SECTION 11-4.24
 AND ALL SUBSECTIONS.
 4. SUBMIT A SANT. AND A WATER RISER
 DIAGRAM IN ISOMETRIC FORM. SHOW ALL PIPE
 SIZES, TRAP, VENT/SANT CONNECTIONS FOR
 THE SANT. AND SHOW ALL PIPE SIZES,
 VALVES, WATER HAMMER ARRESTORS, (IF
 REQUIRED BY SECTION 604.9), AND POINT OF
 CONNECTION. SECTION 104.3.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]