2005-07-27 00:00:00DENIED:
 1.PLANS ARE TO BE SIGNED, SEALED AND
 DATED BY THE ENGINEER PER FS 471.025.
  
 2.PLAN SHEET M0.1 MECHANICAL NOTE #10
 STATES "CONDENSATE SHALL BE SCHEDULE 40
 PVC OR COPPER IF LOCATED IN A RETURN AIR
 PLENUM".PLAN SHEET M 1.1, INDICATES
 RETURN AIR PLENUM THEREFORE PVC WILL NOT
 BE ALLOWED.
  
 3.PLEASE INDICATE IF THE OUTSIDE AIR
 WILL BE REQUIRED TO BE CHANGED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.