| 2005-07-27 00:00:00 | DENIED: | | | 1.PLANS ARE TO BE SIGNED, SEALED AND | | | DATED BY THE ENGINEER PER FS 471.025. | | | | | | 2.PLAN SHEET M0.1 MECHANICAL NOTE #10 | | | STATES "CONDENSATE SHALL BE SCHEDULE 40 | | | PVC OR COPPER IF LOCATED IN A RETURN AIR | | | PLENUM".PLAN SHEET M 1.1, INDICATES | | | RETURN AIR PLENUM THEREFORE PVC WILL NOT | | | BE ALLOWED. | | | | | | 3.PLEASE INDICATE IF THE OUTSIDE AIR | | | WILL BE REQUIRED TO BE CHANGED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|