| Notes |
| Date |
Text |
| 2005-08-05 00:00:00 | ******DENIED****** | | | | | | 1) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION FOR CEILINGS AND WALLS. | | | | | | 2) 2A-10B,C RATED FIRE EXTINGUISHER | | | SHALL BE MOUNTED TO SATISFY THE 75' | | | TRAVEL DISTANCE. | | | | | | 3) CONSTRUCTION, ALTERATION AND | | | DEMOLITION TO COMPLY WITH NFPA 241. | | | | | | 4) SEPARATE SHOP DRAWINGS AND PERMITS | | | ARE REQUIRED FIR FIRE SPRINKLER AND FIRE | | | ALARM REMODEL. | | | | | | | | | MIKE WENNERGREN, CAPTAIN | | | WPBFR(561) 804-4756 | | | PLAN REVIEW(561) 805-6722 |
|