Plan Review Notes
Plan Review Notes For Permit 05070224
Permit Number 05070224
Review Stop E
Sequence Number 1
Notes
Date Text
2005-07-15 00:00:00********** UNSAT ***********
  
 1)NOTE: PLEASE SEE ONY ONE SET OF PLANS
 FOR MP'S WERE SIGNED, DATED AND
 SEALED.
 PLEASE SEE FS 471.025
 THIS IS REQUIRED OF ALL TRADES AND FOR
 ALL SHEETS WHEATHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWERS.
  
 2)NOTE: PLEASE SEE BLDG REVIEW NOTES FOR
 ARCHITECT'S TITLE BLOCK MISSING
 INFORMATION AS REQUIRED UNDER FAC
 61G1-16.004, FS 481.219
 REQUIRED WHEATHER OR NOT COMMENT IS MADE
 BY BLDG REVIEW.
  
 3)NOTE: PLEASE SEE 2002 NEC FOR BRANCH
 CIRCUITS IN KITCHENS WHICH REQUIRES ALL
 15- AND 20-AMPERE, 125-VOLT RECEPTACLES
 IN NONDWELLING-TYPE KITCHENS TO BE GFCI
 PROTECTED. THIS REQUIREMENT APPLIES TO
 EACH AND EVERY 15- AND 20-AMPERE,
 125-VOLT KITCHEN RECEPTACLE, WHETHER OR
 NOT THE RECEPTACLE SERVES COUNTERTOP
 APPLIANCES.
  
 4)NOTE: PLEASE SEE EM/EXT LIGHTING
 CIRCUITS ARE NOTED AS BEING WIRED INTO
 AN EM PANEL?? PLEASE CLARIFY THIS AS IT
 SEEM EM BACK-UP GEN IS HAS BEEN REMOVED.
 PLEASE ALSO SEE CIRCUITING SEEMS TO
 NOTED TO A PANEL "?". PLEASE SEE DUE TO
 CIRCUITING NOT BEING SHOWN, IT IS
 UNCLEAR IF PANELS SUBMITTED CONTAIN
 CIRCUITS?
 PLEASE CLARIFY FIXTURE TYPE "B" FOR
 BATTERY BACK UP?
 IT APPEARS EXT LTS ARE BATTERY BACK-UP.
 PLEASE CLARIFY IF THESE FIXTURES WILL
 NOW BECOME BATTERY BACK. PLEASE ALSO SEE
 LS 101 7-9 FOR CIRCUITING.
 700.12E,700.16 ETC.
 THE BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
  
 PLEASE SEE CONTROL WIRING FOR ATS SHALL
 ALSO BE REMOVED. PLEASE NOTE THIS ON
 PLANS.
 ***************************************
 PLEASE KNOW A GENERATOR WILL NOT BE
 PERMITTED ON ROOF, EVEN IF THERE WAS ONE
 THERE PREVIOUSLY. THIS IS ONLY A NOTE:
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHERREVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 **************************************
 PLEASE BE SURE TO REMOVE ANY OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 POSSIBLE STAMPING. ONE COPY OF
 OLD/VOIDED SHEETS SHALL BE SUBMITTED FOR
 REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  