| Date |
Text |
| 2005-07-15 00:00:00 | ********** UNSAT *********** |
| | |
| | 1)NOTE: PLEASE SEE ONY ONE SET OF PLANS |
| | FOR MP'S WERE SIGNED, DATED AND |
| | SEALED. |
| | PLEASE SEE FS 471.025 |
| | THIS IS REQUIRED OF ALL TRADES AND FOR |
| | ALL SHEETS WHEATHER OR NOT COMMENT IS |
| | MADE BY OTHER REVIEWERS. |
| | |
| | 2)NOTE: PLEASE SEE BLDG REVIEW NOTES FOR |
| | ARCHITECT'S TITLE BLOCK MISSING |
| | INFORMATION AS REQUIRED UNDER FAC |
| | 61G1-16.004, FS 481.219 |
| | REQUIRED WHEATHER OR NOT COMMENT IS MADE |
| | BY BLDG REVIEW. |
| | |
| | 3)NOTE: PLEASE SEE 2002 NEC FOR BRANCH |
| | CIRCUITS IN KITCHENS WHICH REQUIRES ALL |
| | 15- AND 20-AMPERE, 125-VOLT RECEPTACLES |
| | IN NONDWELLING-TYPE KITCHENS TO BE GFCI |
| | PROTECTED. THIS REQUIREMENT APPLIES TO |
| | EACH AND EVERY 15- AND 20-AMPERE, |
| | 125-VOLT KITCHEN RECEPTACLE, WHETHER OR |
| | NOT THE RECEPTACLE SERVES COUNTERTOP |
| | APPLIANCES. |
| | |
| | 4)NOTE: PLEASE SEE EM/EXT LIGHTING |
| | CIRCUITS ARE NOTED AS BEING WIRED INTO |
| | AN EM PANEL?? PLEASE CLARIFY THIS AS IT |
| | SEEM EM BACK-UP GEN IS HAS BEEN REMOVED. |
| | PLEASE ALSO SEE CIRCUITING SEEMS TO |
| | NOTED TO A PANEL "?". PLEASE SEE DUE TO |
| | CIRCUITING NOT BEING SHOWN, IT IS |
| | UNCLEAR IF PANELS SUBMITTED CONTAIN |
| | CIRCUITS? |
| | PLEASE CLARIFY FIXTURE TYPE "B" FOR |
| | BATTERY BACK UP? |
| | IT APPEARS EXT LTS ARE BATTERY BACK-UP. |
| | PLEASE CLARIFY IF THESE FIXTURES WILL |
| | NOW BECOME BATTERY BACK. PLEASE ALSO SEE |
| | LS 101 7-9 FOR CIRCUITING. |
| | 700.12E,700.16 ETC. |
| | THE BRANCH CIRCUIT FEEDING THE UNIT |
| | EQUIPMENT SHALL BE THE SAME BRANCH |
| | CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD |
| | OF ANY LOCAL SWITCHES. |
| | |
| | PLEASE SEE CONTROL WIRING FOR ATS SHALL |
| | ALSO BE REMOVED. PLEASE NOTE THIS ON |
| | PLANS. |
| | *************************************** |
| | PLEASE KNOW A GENERATOR WILL NOT BE |
| | PERMITTED ON ROOF, EVEN IF THERE WAS ONE |
| | THERE PREVIOUSLY. THIS IS ONLY A NOTE: |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHERREVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | ************************************** |
| | PLEASE BE SURE TO REMOVE ANY OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO COMPLETE SETS FOR REVIEW AND |
| | POSSIBLE STAMPING. ONE COPY OF |
| | OLD/VOIDED SHEETS SHALL BE SUBMITTED FOR |
| | REFERENCE ONLY. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |