2005-08-07 00:00:00BUILDING PLAN REVIEW
 PERMIT:05070224
 ADD: 250 S AUSTRALIAN AV# 600
 CONT: SHAKMAN
 TEL: (561)750-8288
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)PROVIDE NOC RECORDED WITH THE CLERK OF
 COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 MISSING THE CERTIFICATE OF AUTHERIZATION
 NUMBER ON PLAN, FAC 61G1-16,004 FL SS
 481.219.
  
 3) OFFICE 604 & 605 MISSING THE 18"
 REQUIRED ON THE PULL SIDE,11-4.13.6
 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 4) SHEET A-3 MISSING EXIT LIGHTS AND
 DIRECTIONALS.1016.1.1 ILLUMINATION OF
 MEANS OF EGRESS SHALL BE PROVIDED IN
 ACCORDANCE WITH THIS SECTION FOR EVERY
 BUILDING AND STRUCTURE.FOR THE
 PURPOSES OF THIS REQUIREMENT, EXIT
 ACCESS SHALL INCLUDE ONLY DESIGNATED
 STAIRS, AISLES, CORRIDORS, RAMPS,
 ESCALATORS AND PASSAGEWAYS LEADING TO
 AN EXIT.FOR THE PURPOSES OF THIS
 REQUIREMENT, EXIT DISCHARGE SHALL
 INCLUDE ONLY DESIGNATED STAIRS,
 AISLES, CORRIDORS, RAMPS, ESCALATORS,
 WALKWAYS AND EXIT PASSAGEWAYS LEADING
 TO A PUBLIC WAY.
  
 5) SHEET A-9 INDICATES WOOD BACKING IN
 WALS AND SUB-BUCKS.609.2.1 TYPE I AND
 TYPE II CONSTRUCTION. PARTITIONS SHALL
 BE CONSTRUCTED OF NONCOMBUSTIBLE
 MATERIALS.
  
 6) SHEET A-3 INDICATES THE USE OF
 SIDELIGHTS FOR VARIOUS OFFICES BUT NO
 MENTION OF SIDELIGHT.2405.2 HAZARDOUS
 LOCATIONS.GLAZING IN AN INDIVIDUAL FIXED
 OR OPERABLE PANEL ADJACENT TO A DOOR
 WHERE THE NEAREST VERTICAL EDGE IS
 WITHIN A 24-INCH (610 MM) RADIUS OF THE
 DOOR IN A CLOSED POSITION AND WHOSE
 BOTTOM EDGE IS LESS THAN 60 INCHES (1524
 MM) ABOVE THE FLOOR OR WALKING SURFACE.
  
 7) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715