| 2005-12-05 00:00:00 | ***UNSAT 2ND REVIEW ***** |
| | |
| | |
| | PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW WHICH STILL NEED TO BE ADDRESSED. |
| | |
| | 1)NOTE: NOTE #1 OK. |
| | |
| | 2)NOTE: NO, ALTHOUGH REPSONSE LTR |
| | MENTIONS THIS SHALL BE UNDER A SEPARATE |
| | PERMIT, THE PLANS DO NOT NOTE THIS. |
| | IF UNDER THIS PERMIT. PLEASE INCLUDE |
| | WIND LOADING FOR SITE LIGHTING POLES. |
| | PLEASE SEE THE WIND LOAD CALCS ARE |
| | REQUIRED AT THIS TIME AND SHALL BE |
| | REVIWED BY BLDG PLAN REVIEW. |
| | |
| | 3)NOTE: NOTE #3 NO, PLEASE INCLUDE |
| | SIZING FOR ALL EXISTING SEC'S. |
| | 215.5 |
| | PLEASE SEE 240.4,310.16 |
| | PLEASE SEE RESPONSE LTR MENTIONS, LOAD |
| | CALCUALTIONS PROVIDED, HOWEVER EXISTING |
| | SEC'S COULD NOT BE LOCATED. |
| | |
| | 4)NOTE: NOTE#4 |
| | ** MOTEL OCCUPANCY** |
| | PLEASE SUBMIT LOAD CALCULATIONS PER |
| | 2002 NEC. |
| | PLEASE ALSO SEE LOAD CALCS FOR SERVICE |
| | ARE TO MEET 220.3,220.10,220.11 ETC. |
| | PLEASE SEE OTHER HOUSE/OFFICE UNIT LOADS |
| | WHICH ARE NOW SHOWN NEED TO BE SHOWN PER |
| | NEC. |
| | PLEASE INCLUDE ALL LOADS OF EXISTING AND |
| | NEW. |
| | 215.5 |
| | |
| | 5)NOTE:NOTE #5 NO, PLEASE CORRELATE |
| | LOADS SHOWN ON PANEL PH WITH LOADS |
| | INDICATED ON PANEL SCHEDULES FOR UNITS. |
| | 215.5 |
| | PLEASE SEE LAODS FOR PANELS,P8,P9 AND |
| | P10 DO CORRELATE. (4.4, 4.6) |
| | |
| | 6)NOTE: NOTE #6 OK. |
| | |
| | 7)NOTE:NOTE # 7 NO, PLEASE SEE |
| | RESPONSE MENTIONS SEE REVISED E-1 AND |
| | E-4, HOWEVER E-1 INDICATES ARC FAULT FOR |
| | RECEPTS ONLY. PLEASE SEE "ALL OUTLETS" |
| | PER PLEASE SEE ARC FAULT PROTECTION |
| | WILL BE REQUIRED UNDER 2002 NEC 210.12 |
| | |
| | |
| | 8)NOTE: NOTE #8 OK. |
| | |
| | 9)NOTE: NOTE #9 OK. |
| | |
| | |
| | 10)NOTE: NOTE #10 OK, HOWEVER NO |
| | VERIFICATION OF SIZING CAN BE DONE, AS |
| | SEC'S ARE NOT SHOWN.PLEASE PROVIDE SIZE |
| | OF EXSITNG TAP/GUTTER BOX. ( LENGTH)? |
| | SIZE SHALL BE VERIFIED FOR NEW OR |
| | EXISTING SEC'S. |
| | 366.6 |
| | |
| | 11)NOTE: PLEASE NOTE,, TYPE OF CONDUIT |
| | FOR FEEDERS TO UNITS IS NOT SHOWN, IF |
| | PVC AND SCH 80, PLEASE SEE CONDUIT FILL |
| | WILL EXCEED PERMITTED FILL FROM TABLES |
| | IN CHAPTER 9. THIS IS ONLY A NOTE: |
| | |
| | PLEASE BE SURE TO SEE ANY POSSIBEL |
| | COMMENTS FROM OTHER TRADES WHICH MAY |
| | AFFECT ELECTRICAL PLANS. |
| | |
| | PLEASE BE SURE TO REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | PLEASE BE SURE TO SUBMIT ONE COPY OF |
| | OLD/VOIDED SHEETS FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |