Plan Review Notes
Plan Review Notes For Permit 05070207
Permit Number 05070207
Review Stop P
Sequence Number 1
Notes
Date Text
2005-08-06 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 FUEL GAS
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT A-1 TOILET ROOM FOR OFFICE SHALL
 BE ACCESSIBLE PER SECTION 11-4.1.6(1)(B)
 SUBMIT A DETAIL SHOWING COMPLIANCE WITH
 SECTIONS 11-4.16, 11-4.19, & 11-4.22 AND
 ALL SUBSECTIONS.
 2. PER TABLE 403.1 A DRINKING FOUNTAIN &
 A SERVICE SINK IS REQUIRED.
 3. SHT A-1 ROOM FINISH SCHEDULE, THE
 WALLS OF ALL PUBLIC RESTROOM SHALL BE
 LINED WITH NONABSORBENT MATERIAL TO
 HEIGHT OF 4' ABOVE THE FLOOR. SECTION
 1204.2. SUBMIT INFORMATION SHOWING
 COMPLIANCE.
 4. ENGINEER SHALL SHOW ALL REQUIRED
 INFORMATION IN THE TITLE BLOCK OF EACH
 SHEET. 61G15-23.002(2) & FS 471.025.
 (PRINTED NAME)
 5. SHT P-2 NO SANT. DRAINAGE PIPING
 SHOWN TO P-4 FIXTURE IN UNIT #3. SECTION
 104.2.1.
 6. SHTS P-2 & P-3 FLOOR DRAIN REQUIRED
 IN LAUNDRY ROOM. SECTION 412.4
 7. SHT P-3 WATER HAMMER ARRESTORS
 REQUIRED AT EACH WASH MACHINE PER
 SECTION 604.9. LOCATE NEXT TO FIXTURES.
 8. SEPARATE GAS PERMIT REQUIRED. SUBMIT
 THE FOLLOWING INFORMATION:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. - THIS INCLUDES THE
 SECTION FROM THE METER TO THE FIRST RISE
 IN THE SYSTEM.
 B. TYPE OF GAS, (LP OR NATURAL)
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 D. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 E. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 G. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 H. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]