| Date |
Text |
| 2005-07-22 00:00:00 | ************* UNSAT *********** |
| | |
| | 1)NOTE: PLEASE INCLUDE ALL INFORMATION |
| | ON TITLE BLOCK AS REQUIRED UNDER FAC |
| | 61G15-23.002, PLEASE SEE MISSING PRINTED |
| | NAME. |
| | |
| | 2)NOTE: PLEASE INCLUDE WINDING LOADING |
| | FOR SITE LIGHTING POLES. |
| | PLEASE SEE THE WIND LOAD CALCS ARE |
| | REQUIRED AT THIS TIME AND SHALL BE |
| | REVIWED BY BLDG PLAN REVIEW. |
| | |
| | 3)NOTE: PLEASE INCLUDE SIZING FOR ALL |
| | EXISTING SEC'S. |
| | 215.5 |
| | PLEASE SEE 240.4,310.16 |
| | |
| | 4)NOTE: PLEASE SUBMIT LOAD CALCULATIONS |
| | PER 2002 NEC. PLEASE SEE HOUSE LOADS ARE |
| | SHOWN BEING DERATED WITH DWELLING UNIT |
| | LOADS WHICH IS NOT PERMITTED. |
| | PLEASE ALSO SEE LOAD CALCS FOR SERVICE |
| | ARE TO MEET 220.3,220.10,220.11 ETC. |
| | PLEASE SEE OTHER HOUSE/OFFICE UNIT LOADS |
| | ARE NOT SHOWN AND/OR ARE NOT INCLUDED IN |
| | SERVICELOAD CALCS. |
| | PLEASE INCLUDE ALL LOADS OF EXISTING AND |
| | NEW. |
| | 215.5 |
| | |
| | 5)NOTE: PLEASE CORRELATE LOADS SHOWN ON |
| | PANEL PH WITH LOADS INDICATED ON PANEL |
| | SCHEDULES FOR UNITS. |
| | 215.5 |
| | PLEASE SEE LAODS FOR PANELS,P8,P9 AND |
| | P10 DO CORRELATE. |
| | |
| | 6)NOTE: PLEASE SEE MIN CIRCUIT FOR BATHS |
| | ARE TO MEET 210.52,210.11C3, MUST BE 20A |
| | AND #12. |
| | |
| | 7)NOTE: PLEASE SEE ARC FAULT PROTECTION |
| | WILL BE REQUIRED UNDER 2002 NEC 210.12 |
| | PLEASE SEE "ALL OUTLETS" , SD'S, LTS, |
| | FANS, RECEPTS ETC ARE TO AHVE ARC FAULT |
| | PROTECTED CIRCUITS. |
| | |
| | 8)NOTE: PLEASE A MIN OF 1500 VA SHALL |
| | APPLY TO LAUNDRY CIRCUIT. |
| | PLEASE SEE 210.11C2, 220.16B |
| | |
| | 9)NOTE: PLEASE SEE 250.6,250.24, |
| | EQUIPMENT GROUNDING CONDUCTORS SHALL NOT |
| | BE INSTALLED UNTIL AFTER THE FIRST MEANS |
| | OF DISCONNECT. |
| | PLEASE SEE #3 EG SHOWN FROM GUTTER TO |
| | NEW METER/ MAIN. |
| | |
| | 10)NOTE: PLEASE PROVIDE SIZE OF EXSITNG |
| | TAP/GUTTER BOX. |
| | SIZE SHALL BE VERIFIED FOR NEW OR |
| | EXISTING SEC'S. |
| | 366.6 |
| | |
| | PLEASE BE SURE TO SEE ANY POSSIBEL |
| | COMMENTS FROM OTHER TRADES WHICH MAY |
| | AFFECT ELECTRICAL PLANS. |
| | |
| | PLEASE BE SURE TO REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | PLEASE BE SURE TO SUBMIT ONE COPY OF |
| | OLD/VOIDED SHEETS FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |