| 2005-08-07 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05070207 |
| | ADD: 3712 BROADWAY |
| | CONT: K& M COMMERCIAL CONSTRUCTION |
| | TEL: (561)248-9648 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PERMIT APPLICATION INDICATES WORK IS |
| | TO BE COMPLETED AT 3712 BROADWAY. WORK |
| | TO BE COMPLETED AT 3702 BROADWAY. |
| | CORRECT APPLICATION AND PROPERTY CONTROL |
| | NUMBER. |
| | |
| | 2) PROVIDE A SURVEY FOR 3702 BROADWAY. |
| | THE NORTH SIDE OF BUILDING MAY HAVE |
| | TABLE 600 ISSUES. |
| | |
| | 3)PROVIDE NOC RECORDED WITH THE CLERK OF |
| | COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 4)3401.2.2.1 IF THE OCCUPANCY |
| | CLASSIFICATION OR OCCUPANCY |
| | SUBCLASSIFICATIONS OF ANY EXISTING |
| | BUILDING OR STRUCTURE IS CHANGED, THE |
| | BUILDING, ELECTRICAL, GAS, MECHANICAL |
| | AND PLUMBING SYSTEMS SHALL BE MADE TO |
| | CONFORM TO THE INTENT OF THE TECHNICAL |
| | CODES AS REQUIRED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 6) FL BLD CODE CHAP 13 ENERGY EFFICENCY |
| | PROVIDE ENERGY CALS/ W MANUAL "J" |
| | |
| | 7) 1203.1.3 ATTICS NOT USED FOR |
| | HABITATIONAL PURPOSES SHALL HAVE |
| | PROVISIONS FOR THE EMISSION OF EXCESS |
| | HEAT. |
| | |
| | 8)2309.6 ACCESS TO ATTIC SPACE. ATTIC |
| | SPACES SHALL BE PROVIDED WITH AN |
| | INTERIOR ACCESS OPENING NOT LESS THAN |
| | 20X36 INCHES (508X914 MM).ACCESS |
| | OPENING SHALL BE ACCESSIBLE AND PROVIDED |
| | WITH A LID OR DEVICE THAT MAY BE |
| | EASILY REMOVED OR OPERATED.WHEN |
| | MECHANICAL EQUIPMENT IS TO BE INSTALLED |
| | IN THE ATTIC, IT SHALL BE INSTALLED IN |
| | ACCORDANCE WITH ?M306.3 OF FLORIDA |
| | BUILDING CODE, MECHANICAL.ACCESS IS |
| | NOT REQUIRED WHEN THE CLEAR HEIGHT |
| | OF THE ATTIC SPACE, MEASURED AT THE ROOF |
| | PEAK, IS LESS THAN 24 INCHES (610 |
| | MM). |
| | |
| | 9) PROVIDE CALCULATIONS:1203.1.4 EXCEPT |
| | AS OTHERWISE PROVIDED HEREIN, REQUIRED |
| | WINDOWS SHALLHAVE GLAZED OPENINGS OF |
| | CLEAR GLASS OF AREA NOT LESS THAN 8% OF |
| | THE FLOOR AREA OF THE ROOM SERVED. |
| | |
| | 10) DOORS SEE LABEL "C": 11-4.13.5 CLEAR |
| | WIDTH. DOORWAYS SHALL HAVE A MINIMUM |
| | CLEAR OPENING OF32 INCHES (815 MM) |
| | WITH THE DOOR OPEN 90 DEGREES, MEASURED |
| | BETWEEN THEFACE OF THE DOOR AND THE |
| | OPPOSITE STOP (SEE FIGURE 11-24(A), |
| | FIGURE 11-24(B), FIGURE 11-24(C), AND |
| | FIGURE 11-24(D)).OPENINGSMORE THAN |
| | 24 INCHES (610 MM) IN DEPTH SHALL COMPLY |
| | WITH 11-4.2.1 AND 11-4.3.3 (SEE FIGURE |
| | 11-24(E)). |
| | |
| | 11)11-9.1.2 ACCESSIBLE UNITS, SLEEPING |
| | ROOMS, AND SUITES. ACCESSIBLESLEEPING |
| | ROOMS OR SUITES THAT COMPLY WITH THE |
| | REQUIREMENTS OF ?11-9.2.1TO ?11-9.2.2 |
| | (REQUIREMENTS FOR ACCESSIBLE UNITS, |
| | SLEEPING ROOMS, ANDSUITES) SHALL BE |
| | PROVIDED IN CONFORMANCE WITH THE TABLE |
| | BELOW.INADDITION, IN HOTELS, OF 50 |
| | OR MORE SLEEPING ROOMS OR SUITES, |
| | ADDITIONALACCESSIBLE SLEEPING ROOMS |
| | OR SUITES THAT INCLUDE A ROLL-IN SHOWER |
| | SHALL ALSO BE PROVIDED IN CONFORMANCE |
| | WITH THE TABLE BELOW.SUCH |
| | ACCOMMODATIONS SHALL COMPLY WITH THE |
| | REQUIREMENTS OF ?11-9.2, ?11-4.21, |
| | AND FIGURE 11-57(A) OR FIGURE 11-57(B). |
| | |
| | 12) PLANS DO NOT INDICATE FLOOR LEVEL ON |
| | THE EXTERIOR OF THE EXTERIOR DOORS, |
| | INDICATE GRADE IN RELATIONSHIP TO FINISH |
| | FLOOR LEVEL. 11-4.3.2(3) AT LEAST ONE |
| | ACCESSIBLE ROUTE SHALL CONNECT |
| | ACCESSIBLE BUILDING OR FACILITY |
| | ENTRANCES WITH ALL ACCESSIBLE SPACES AND |
| | ELEMENTS AND WITH ALL ACCESSIBLE |
| | DWELLING UNITS WITHIN THE BUILDING OR |
| | FACILITY. |
| | |
| | 13) 11-4.6.1 MINIMUM NUMBER. PARKING |
| | SPACES REQUIRED TO BE ACCESSIBLE BY |
| | 11-4.1 SHALL COMPLY WITH ?11-4.6.2 |
| | THROUGH ?11-4.6.5.PASSENGER LOADING |
| | ZONES REQUIRED TO BE ACCESSIBLE BY |
| | 11-4.1 SHALL COMPLY WITH 11-4.6.5 AND |
| | 11-4.6.6. |
| | |
| | 14) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 15)FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) DOORS |
| | B) WINDOWS |
| | |
| | 15) BATHROOMS:1204.2 SURROUNDING |
| | MATERIALS; THE WALLS & FLOORS OF ALL |
| | PUBLIC REST- ROOMS SHALL BE LINED WITH |
| | NONABSORBANT MATERIALS TO A HEIGTH OF |
| | 4'-0" ABOVE THE FLOOR. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |