Plan Review Notes
Plan Review Notes For Permit 05070203
Permit Number 05070203
Review Stop M
Sequence Number 1
Notes
Date Text
2005-08-01 00:00:00MECH. PLAN REVIEW:
  
 MECH. PROVISO:
  
 IF ELECT. GENERATOR IS 10 FEET FROM
 BUILDING AND EXHAUST IS DIRICTED AWAY
 FROM BUILDING, THIS MEET INTENT OF MECH.
 CODE.
 2001 FBC/M 804.3.3 TERMINATION.
  
 2001 FBC/M SECTION 915
 REQUIREMENT OF NFPA 37 8.2.3.2
 EXHAUST SYSTEM TERMINATION.
  
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
  
 PLEASE CALL IF THEAR ANY QUESTIONS.
  
  