 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE VERIFY THE TRANSFER SWITCH
 RATING OF 600 AMPS FOR A 136 AMP LOAD.
  
 2} THE TRANSFER SWITCH MUST BE SERVICE
 RATED PER 225.36. PLEASE INDICATE SAME.
  
 3} THE RISER DOES NOT SHOW HOW THE
 CIRCUITS WILL BE LIMITED TO THE
 CALCULATIONS INDICATED.THE ATS APPEARS
 TO FEED ALL 4 HOUSE PANELS.
  
 4} A DEMAND FACTOR MAY BE TAKEN ON THE
 LIGHTING CIRCUITS ONLY. THE REST OF THE
 INTENDED LOAD MUST BE AT 100%. SEE
 702.5.
  
 5} THE DESIGNER OF RECORD MUST SIGN AND
 SEAL THE PLAN. SEE 61G15-23.002 FAC.,471
 .025 FS.
  