| 2005-07-29 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE VERIFY THE TRANSFER SWITCH | | | RATING OF 600 AMPS FOR A 136 AMP LOAD. | | | | | | 2} THE TRANSFER SWITCH MUST BE SERVICE | | | RATED PER 225.36. PLEASE INDICATE SAME. | | | | | | 3} THE RISER DOES NOT SHOW HOW THE | | | CIRCUITS WILL BE LIMITED TO THE | | | CALCULATIONS INDICATED.THE ATS APPEARS | | | TO FEED ALL 4 HOUSE PANELS. | | | | | | 4} A DEMAND FACTOR MAY BE TAKEN ON THE | | | LIGHTING CIRCUITS ONLY. THE REST OF THE | | | INTENDED LOAD MUST BE AT 100%. SEE | | | 702.5. | | | | | | 5} THE DESIGNER OF RECORD MUST SIGN AND | | | SEAL THE PLAN. SEE 61G15-23.002 FAC.,471 | | | .025 FS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|