| Plan Review Notes For Permit 05070203 |
| Permit Number |
05070203 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-10 00:00:00 | ****CORRECTIONS**** | | | | | | MYRON JACOBS, BUILDING PLANS EXAMINER | | | 561-805-6726 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC*CITY OF WESTPALM BEACH | | | AMENDMENTS. TO THE FBC2001 | | | | | | BLDG: PROVISO. | | | | | | 1.)PROVIDE ANCHORING INFORMATION TO | | | COMPLY WITH FBC1606.1.3; STRUCTURAL | | | MEMBERS AND SYSTEMS, AND COMPONENTS AND | | | CLADDING IN A BUILDING OR STRUCTURE | | | SHALL BE ANCHORED TO RESIST WIND-INDUCED | | | OVERTURNING, UPLIFT AND SLIDING AND TO | | | PROVIDE CONTINUOUS LOAD PATHS FOR THESE | | | FORCES TO THE FOUNDATION.WHERE A | | | PORTION OF THE RESISTANCE TO THESE | | | FORCES IS PROVIDED BY DEAD LOAD, THE | | | MINIMUM DEAD LOAD LIKELY TO BE IN PLACE | | | DURING A DESIGN WIND EVENT SHALL BE | | | USED. | | | | | | | | | 2.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | BUILDING PLAN REVIEW | | | MYRON JACOBS | | | TEL: (561)805-6726 | | | FAX: (561)659-8026 |
|