| Plan Review Notes For Permit 05070199 |
| Permit Number |
05070199 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-10 00:00:00 | MECH. PLAN REVIEW: | | | | | | PROVISO: | | | 1. A.H.U. REQUIRES AUX. DRAIN PAN AND | | | WITH DRANE PAN PROTECTION. 2003 FBC/M | | | 307.2.3 . | | | | | | 2.BEDROOM REQUIRES R/A 2003 FBC/M 601.4 | | | . | | | | | | 3. A.H.U. MECHANICAL CLOSIT REQUIRES. | | | FBC CHAPTER 13 610.1 ABC .7. | | | | | | 4. A.H.U. SPACE PROVIDED FBC CHAPTER 13 | | | 6610 ABC 3.0.3. . | | | | | | 5. R/A THROUGH KITCHED WILL SPREAD KIT. | | | ODERS THROUGH HOUSE. | | | R/A SHOUGH BE DIRECTED THOUGH LIVING | | | AREA. | | | | | | PAT RAFTER561/805/6728 OR 805/6719 | | | PATTY KRAUSS. | | | | | | PLEASE CALL IF THEAR ANY QUESTIONS. | | | | | | | | | | | 2005-07-11 00:00:00 | -----------------DENIED----------------- | | | | | | BLDG 2 - AIR HANDLING UNIT SHALL NOT BE | | | LOCATED IN LAUNDRY ROOM PER FBC CH | | | 13,SEC.610.1.ABC.3.7 | | | | | | RONALD J REGUEIRO | | | 561-805-6734 | | | [email protected] |
|