| 2005-09-02 00:00:00 | ************ UNSAT 2ND REVIEW ******** |
| | |
| | 1)NOTE: PLEASE SEE COMMENTS FROM |
| | PREVIOUS REVIEW BY MR. BILL TROBAUGH. |
| | PLEASE INDICATE OCP FEEDING NEW PANEL. |
| | PLEASE SEE MISSING EQUIPMENT GROUNDING |
| | CONDUCTOR PER 250.110,250.122 |
| | |
| | 2)NOTE: PLEASE SEE HAND DRAWN LOAD CALCS |
| | AND RISER WAS SUBMITTED HOWEVER RISER |
| | DOES NOT CORRELATE WITH PLANS. |
| | PLEASE SEE LOAD CALCULATIONS SUBMITTED |
| | ARE REQUIRED TO MEET NEC 220.31B, |
| | 220.215.3,680.9 |
| | PLEASE SEE A/C AND HEAT PUMP LOADS MAY |
| | NOT BE DE-RATED AT 40%??? |
| | PLEASE SEE ALL CONTINUOUS LOADS ARE TO |
| | BE SHOWN AT 125%, (HEAT PUMP, POOL PUMP) |
| | PLEASE SEE OTHER INFORMATION AS |
| | PREVIOUSLY REQUESTED CAN NOT BE VERIFIED |
| | AT THIS TIME. |
| | 215.3,215.5,230.42, 680.9, 240.4,310.16 |
| | ETC. |
| | |
| | 3)NOTE: PLEASE SUBMIT MANUFACTURE |
| | CUT/SPEC SHEETS ON NEW PROPOSED HEAT |
| | PUMP. THIS MUST INDICATE THE LISTING |
| | FROM A NRTL. (NATIONALLY RECOGNIZED |
| | TESTING LAB.) |
| | |
| | 4)NOTE: PLEASE SEE COPY OF FS |
| | 553.80(2)(B) ATTACHED WITH RESPECT TO |
| | THE DESIGN PROFESSIONAL AND PLANS WITH |
| | REPEAT CODE COMPLIANCE COMMENTS. |
| | THIS IS ONLY A NOTICE GIVEN AT THIS |
| | TIME. |
| | |
| | 5)NOTE: PLEASE SEE WHEN ADDITTIONAL |
| | PLANS FOR LOADS CALCS ETC IS SUBMITTED, |
| | MUST BE TWO COPIES AND EACH MUST CONTAIN |
| | THE PRINTED NAME AND SIGNATURE OF THE |
| | PERSON RESPONSIBLE FOR PLANS/DRAWINGS. |
| | FBC 104.2.1, CITY-WIDE ADMINISTRATIVE |
| | CODE. |
| | |
| | PLEASE SUBMIT THE ABVOE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |