2005-07-20 00:00:00 
 DENIED
 ~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
  
 1} PLEASE SUBMIT DETAILS FOR THE PANEL
 SHOWN ON THE SCHEMATIC, FEEDER AND CONDU
 IT SIZE AND TYPE, PANEL RATING AND OCP,
 PANEL SCHEDULE AND COMPUTED LOAD, ETC.
 IF AN ELECTRIC HEATER IS TO BE INSTALLED
 PLEASE SUBMIT CALCULATIONS FOR THE MAIN
 SERVICE.
  