| 2005-07-12 00:00:00 | ********* UNSAT ********* |
| | |
| | 1)NOTE: PLEASE SEE 310.16,240.4 FOR MIN |
| | SIZING FOR FEEDERS FROM 200A MAIN |
| | DISCONNECT TO INSIDE PANEL "A". PLEASE |
| | SEE MAIN IS SHOWN W/ 200A OCP ON |
| | CONDUCTORS ONLY RATED FOR 150A'S. |
| | |
| | 2)NOTE: PLEASE SEE 700.12E FOR |
| | CIRCUITING OF EM/EXT LTS. THE BRANCH |
| | CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL |
| | BE THE SAME BRANCH CIRCUIT AS THAT |
| | SERVING THE NORMAL LIGHTING IN THE AREA |
| | AND CONNECTED AHEAD OF ANY LOCAL |
| | SWITCHES. |
| | |
| | 3)NOTE: PLEASE SEE THE ENGINEER AS SHOWN |
| | ON TITLE BLOCK RESPONSIBLE FOR DESIGN |
| | AND/OR PLANS, SHALL SIGN, DATE AND SEAL |
| | PLANS AS REQUIRED UNDER FS 471.025 |
| | PLEASE SEE THIS IS REQUIRED OF ALL SAID |
| | SHEETS WHEATHER OR NOT COMMENT IS MADE |
| | BY OTHER TRADES. |
| | |
| | PLEASE BE SURE TO REMOVE ANY OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. ONE COPY OF OLD SHEETS SHOULD |
| | BE SUBMITTED FOR REFERENCE ONLY. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESTITATE IN CONTACTING |
| | THIS OFFICE. |
| | |