Plan Review Notes
Plan Review Notes For Permit 05070142
Permit Number 05070142
Review Stop P
Sequence Number 1
Notes
Date Text
2005-07-25 00:00:00DENIED;
 1.PUMPS AND EQUIPMENT SHALL BE MOUNTED
 ON A SUBSTANTIAL BASE. SLAB SHALL BE A
 NOMINAL 4" THICK. SEC 424.2.7.2.
 (DETAIL)
 2.VALVES SHALL BE MADE OF MATERIALS THAT
 ARE APPROVED IN FBC PLUMBING. THEY WILL
 BE READILY ACCESSIBLE FOR MAINT.AND
 REMOVAL. SEC. 424.2.8.2 ALSO 424.2.8.3
 AND 424.2.8.4 ADD TO NOTES.PURPLE PRIMER
 REQUIRED ON PVC PIPING SEC 605.21. (ADD
 TO NOTES)
 3.ALL WATER HEATER EQUIPMENT SHALL BE
 INSTALLED WITH FLANGES OR UNION
 CONNECTIONS ADJACENT TO HEATER.
 424.2.14.4. (ADD TO NOTES)
 4.GAS PIPING SHALL COMPLY WITH FBC 2001
 FUEL GAS. SEPARATE PLANS AND PERMIT
 REQUIRED. SEC.424.2.15. (ADD TO NOTES.
 PLUMBING PLAN REVIW BY;
 JOHN LEECH
 805-6695