| Plan Review Notes For Permit 05070142 |
| Permit Number |
05070142 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-25 00:00:00 | DENIED; | | | 1.PUMPS AND EQUIPMENT SHALL BE MOUNTED | | | ON A SUBSTANTIAL BASE. SLAB SHALL BE A | | | NOMINAL 4" THICK. SEC 424.2.7.2. | | | (DETAIL) | | | 2.VALVES SHALL BE MADE OF MATERIALS THAT | | | ARE APPROVED IN FBC PLUMBING. THEY WILL | | | BE READILY ACCESSIBLE FOR MAINT.AND | | | REMOVAL. SEC. 424.2.8.2 ALSO 424.2.8.3 | | | AND 424.2.8.4 ADD TO NOTES.PURPLE PRIMER | | | REQUIRED ON PVC PIPING SEC 605.21. (ADD | | | TO NOTES) | | | 3.ALL WATER HEATER EQUIPMENT SHALL BE | | | INSTALLED WITH FLANGES OR UNION | | | CONNECTIONS ADJACENT TO HEATER. | | | 424.2.14.4. (ADD TO NOTES) | | | 4.GAS PIPING SHALL COMPLY WITH FBC 2001 | | | FUEL GAS. SEPARATE PLANS AND PERMIT | | | REQUIRED. SEC.424.2.15. (ADD TO NOTES. | | | PLUMBING PLAN REVIW BY; | | | JOHN LEECH | | | 805-6695 |
|