| 2005-09-10 00:00:00 | ******* UNSAT ******** |
| | |
| | 1)NOTE: PLEASE SEE ELECTRICAL PLANS FROM |
| | ENGINEER OF RECORD ARE REQUIRED TO BE |
| | SIGNED,DATED AND SEALED AS REQUIRED |
| | UNDER FAC 61G15-23.002, FS 471.025 |
| | PLEASE SEE ONE SET. |
| | |
| | 2)NOTE: PLEASE SEE RESPONSE LTR MENTIONS |
| | A NOTE WAS ADDED TO PLANS WITH RESPECT |
| | TO GFI PROTECTION FOR ALL 15/20A 125V |
| | RECEPTS IN KITCHEN IN NON-DWELLING UNITS |
| | PER 2002 NEC 210.8B3, HOWEVER THIS NOTE |
| | COULD NOT BE LOCATED? |
| | |
| | 3)NOTE: PLEASE SEE RESPONSE LTR FROM |
| | ARCHITECT MENTIONS TO SEE ENGINEER'S |
| | RESPONSE FOR REQUIRED EM / EXT LTS, |
| | HOWEVER ENGINEER'S RESPONCE LTR DOES NOT |
| | MENTION THIS. PLEASE ALSO SEE PLANS SEEM |
| | TO ONLY INDICATE NEW EXT LTS? |
| | PLEASE SEE FIRE REVIEW COMMENTS. |
| | NFPA-101 7.8, 7.9 |
| | |
| | PLEASE REMOVE ANY OLD/VOIDED SHEETS FROM |
| | SETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | |
| | PLEASE BE SURE TO SEE ANY POSSIBLE |
| | COMMENTS FROM OTHER REVIEWER(S) WHICH |
| | MAY AFFECT ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |