| 2005-07-12 00:00:00 | ******* UNSAT ******* |
| | |
| | 1)NOTE: PLEASE PROVIDE KW RATINGS FOR |
| | EQUIPMENT ON PANEL SCHEDULES. |
| | PLEASE SHOW ALL TRACK LIGHTING AND ANY |
| | SHOW/WINDOW RECEPTS CIRCUITS PER |
| | 220.12A&B. |
| | PLEASE DOUBLE CHECK ADDED AMERAGES |
| | SHOWN, "A" PHASE. |
| | 215.5,220 |
| | |
| | 2)NOTE: PLEASE SEE 210.8B3 UNDER 2002 |
| | NEC WHICH REQUIRES ALL 15- AND |
| | 20-AMPERE, 125-VOLT RECEPTACLES IN |
| | NONDWELLING-TYPE KITCHENS TO BE GFCI |
| | PROTECTED. THIS REQUIREMENT APPLIES TO |
| | EACH AND EVERY 15- AND 20-AMPERE, |
| | 125-VOLT KITCHEN RECEPTACLE, WHETHER OR |
| | NOT THE RECEPTACLE SERVES COUNTERTOP |
| | APPLIANCES. |
| | |
| | 3)NOTE: PLEASE SHOW ALL OTHER ELEC WHICH |
| | IS EXISTING? UNABLE TO VERIFY LOADS AS |
| | INDICATED AT THIS TIME. |
| | PLEASE SEE PANEL SEEMS TO BE GETTING |
| | VERY CLOSE TO EXCEEDING CAPACITY AND |
| | THERE MAY BE A POSSIBLE NEED FOR |
| | UPGRADING. |
| | ALL LOADS NEED TO VERIFIED AT THIS TIME. |
| | 215.5 |
| | |
| | 4)NOTE: PLEASE SEE CIRCUITING FOR WHAT |
| | APPEARS TO BE A "WALK-IN COOLER". SHOWS |
| | N-2,4, HOWEVER PANEL SCHEDULE INDICATES |
| | THIS CIRCUIT AS CONVECTION OVEN? |
| | |
| | 5)NOTE: PLEASE SEE PLANS INDICATE AN |
| | EXISTING WATER HEATER, HOWEVER THIS IS |
| | NOT ON PANEL SCHEDULE OR LOAD CALCS. IS |
| | THIS WH BEING REMOVED? |
| | |
| | 6)NOTE: PLEASE MAKE NOTE OR REFERENCE TO |
| | NEW OR EXSITNG SHUNT-TRIPS FOR HOOD? |
| | NFPA-96 |
| | |
| | 7)NOTE: PLEASE VERIFY ALL KITCHEN |
| | EQUIPMENT WHICH MAY NOT BE |
| | THERMOSTATICALLY CONTROLLED. (SOUP |
| | WELLS)? IF NOT, PLEASE SEE CONTINUOUS |
| | LOADS AT 125% FOR 3OR MORE HRS. THIS IS |
| | ONLY A NOTE. |
| | |
| | 8)NOTE: PLEASE SEE ARCH FIRM'S LICENSE |
| | NUMBER AS PRINTED ON PLANS DOES NOT SEEM |
| | TO CORRELATE WITH STATE DBPR SITE. |
| | PLEASE VERIFY AND INCLUDE LICENSE NUMBER |
| | AS REQUIRED. FAC 61G1-16.004. |
| | PLEASE SEE PRINT-OUT FROM STATE SHOWS |
| | OTHER FIRMS/NAMES. A COPY OF PRINT-OUT |
| | IS ATTACHED TO NOTES. |
| | THIS IS NOTED FOR ARCHITECTUAL FIRM ONLY |
| | AND NOT FOR ENGINEERING FIRM. |
| | |
| | 9)NOTE: PLEASE SEE SOME EQUIPMENT ON |
| | PLANS NOT CIRCUITED AND/OR NOTED ON |
| | PANEL SCHEDULE."LO-BOYS"? |
| | |
| | 10)NOTE: PLEASE SEE PLANS ARE DATED BY |
| | ENGINEER AS 10/5/05? MISPRINT? SHOULD |
| | READ 5/10/05? |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STMAPING. |
| | ONE SET OF OLD/VOIDED SHEETS SHOULD BE |
| | SUBMITTED FOR REFERENCE ONLY. |
| | |
| | PLEASE SEE OTHER COMMENTS FROM OTHER |
| | REVIEWER(S) WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |