| 2005-08-07 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05070124 |
| | ADD: 460 S ROSEMARY AV# 182 |
| | CONT: ANDERSON-MOORE |
| | TEL: (561)662-1819 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2)FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, THERE |
| | SEEMS TO BE A DISCREPANCY AS TO THE |
| | SUITE NUMBER 180 VS 182. PLANS INDICATE |
| | 180. |
| | |
| | 3) A-1 INDICATES THE REUSE OF STOREFRONT |
| | DOR, BUT THERE IS A NEW SIDELIGHT NEXT |
| | TO THE DOOR REQUIRING PRODUCT APPROVAL. |
| | |
| | THE OTHER ISSUE IS THE EXISTING DOOR |
| | LARGE MISSLE IMPACT RATED? |
| | |
| | 4) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 5)704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| | STOP PARTITIONS, HORIZONTAL EXIT PART- |
| | ITIONS, EXIT ENCLOSURES, AND FIRE |
| | RATED WALLS REQUIRED TO HAVE PROTECTED |
| | OPENINGS SHALL BE EFFECTIVELY AND |
| | PERMANETLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE |
| | AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| | TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| | CEILING CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| | PROTECT ALL OPENINGS". |
| | |
| | 6)11-5.2 COUNTERS AND BARS.WHERE FOOD OR |
| | DRINK IS SERVED AT COUNTERS EXCEEDING 34 |
| | IN. (865 MM) INHEIGHT FOR CONSUMPTION |
| | BY CUSTOMERS SEATED ON STOOLS OR |
| | STANDING AT THE COUNTER, A PORTION OF |
| | THE MAIN COUNTER WHICH IS 60 IN. (1525 |
| | MM) IN LENGTH MINIMUM SHALL BE PROVIDED |
| | IN COMPLIANCE WITH ?11-4.32 OR SERVICE |
| | SHALL BE AVAILABLE AT ACCESSIBLE TABLES |
| | WITHIN THE SAME AREA. |
| | |
| | 7)BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |
| | |
| | |
| | |
| | |
| | |