| Plan Review Notes For Permit 05070120 |
| Permit Number |
05070120 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-08-11 00:00:00 | **** UNSAT 3RD REVIEW **** | | | | | | PLEASE SEE NOTES BELOW, CARRIED OVER | | | FROM PREVIOUS REVIEW. | | | | | | 1)NOTE: PLEASE SEENOTE #2 SECION ONE | | | OF PREVIOUS REVIEW. | | | PLEASE SEE ALL RECEPT CIRCUITS ARE STILL | | | BEING SHOWN WITH LOADS EXCEEDING RATING | | | OF CIRCUIT. | | | PLEASE SEE A MAX OF 1920VA IS ERMITTED | | | ON A 20A BRANCH CIRCUIT. PLEASE SEE | | | 220.13 FOR 180VA PER RECEPT WHEN RECEPT | | | LOADS ARE KNOW. | | | PLEASE SEE THIS WILL AFFECT CIRCUITING | | | AS SHOWN ON PLANS. | | | | | | 2)NOTE: PLEASE SEE PREVIOUS REVIEW | | | REQUESTED ALL OLD/VOIDED SHEETS TOBE | | | REMOVED FROM SETS AND INSERT NEW REVISED | | | SHEETS INTO COMPLETE SETS FOR REVIEW AND | | | STAMPING. | | | | | | 3)NOTE: PLEASE SEE COPY OF FS | | | 553.80(2)(B) WITH RESPECT TO DESIGN | | | PROFESSIONAL AND COMMENTS FOR CODE | | | COMPLIANCE 3 OR MORE TIMES. THIS IS ONLY | | | A NOTICE GIVEN AT THIS TIME. | | | | | | *** PLEASE SEE COMMENTS FROM FIRE, BLDG | | | AND PLUMB **** | | | PLEASE SEE FIRE REVIEW COMMENTS AS THEY | | | WILL AFFECT ELECTRICAL PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|