| 2005-07-28 00:00:00 | **********UNSAT ************* |
| | |
| | 1)NOTE: PLEASE SEE NOTE #2 FROM PREVIOUS |
| | REVIEW WHICH REQUIRED ALL CIRCUITING FOR |
| | EM/EXT LTS PER 700.12E. |
| | PLEASE SEE THE BRANCH CIRCUIT FEEDING |
| | THE UNIT EQUIPMENT SHALL BE THE SAME |
| | BRANCH CIRCUIT AS THAT SERVING THE |
| | NORMAL LIGHTING IN THE AREA AND |
| | CONNECTED AHEAD OF ANY LOCAL SWITCHES. |
| | PLEASE ALSO SEE LOW VOLTAGE FIRE DEVICES |
| | ARE NOTED AS BEING WIRED TO EM CIRCUIT? |
| | PLEASE SEE THESE SHOULD NOT BE WIRED |
| | INTO THE 120V CIRCUITING. |
| | |
| | 2)NOTE: PLEASE SEE CIRCUITING NOW SHOWN |
| | FOR NEW RECEPTS, HOWEVER PLEASE SEE MAX |
| | KVA FOR EACH 20A BRANCH CIRCUIT IS 1920 |
| | VA. PLEASE SEE 220.13 FOR RECEPT LOADS |
| | IN NON-DWELLING INSTALLATIONS.(180VA PER |
| | RECEPT). |
| | ** PLEASE ALSO SEE ALL ALL LOW VOLTAGE |
| | "DATA/PHONE" OUTLETS BEING |
| | WIRED/CIRCUITED TO THE LOCAL 120V RECEPT |
| | CIRCUIT?? |
| | PLEASE CORRECT MISPRINT? |
| | |
| | 3)NOTE: PLEASE SEE TWO CIRCUIT #26'S |
| | SHOWN ON PANEL SCHEDULE. |
| | 215.5 |
| | |
| | PLEASE REMOVE OLD/VOIDED SHEETS AND ONLY |
| | INSERT NEW REVISED SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | ONE COPY OF OLD/VOIDED SHEETS SHALL BE |
| | SUBMITTED FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |