Plan Review Notes
Plan Review Notes For Permit 05070120
Permit Number 05070120
Review Stop P
Sequence Number 1
Notes
Date Text
2005-07-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS CERTIFICATE OF
 AUTHORIZATION IS REQUIRED IN THE TITLE
 BLOCK OF THE INCORPORATED ARCHITECTURAL
 BUSINESS PER FAC 61G1-16.004(2) AND FS
 481.219.
 2. SUBMIT A DETAIL FOR THE BREAKROOM
 SINK SHOWING THE FOLLOWING:
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCE
 C. 11-4.24.4 SINK DEPTH
 D. 11-4.24.5 CLEAR FLOOR SPACE -
 FORWARD APPROACH REQUIRED EXTENDING A
 MAXIMUM OF 19" UNDERNEATH THE SINK. -
 CABINET DOORS IN CLEAR FLOOR SPACE NOT
 APPROVED.
 E. 11-4.24.6 EXPOSED PIPES AND SURFACES
 F. 11-4.24.7 FAUCETS
 3. SUBMIT A SANITARY RISER DIAGRAM IN
 ISOMETRIC FORM, SHOWING ALL PIPE SIZES,
 VENTS, AND POINTS OF CONNECTIONS.
 SECTION 104.3.1.1.
 4. SUBMIT A WATER RISER DIAGRAM IN
 ISOMETRIC FORM, SHOWING ALL PIPE SIZES,
 VALVES, AND POINTS OF CONNECTION.
 SECTION 104.3.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  
  
 (PER CONVERSATION WITH JEROME BROMIEL -
 NO PLUMBING WORK WILL BE DONE ON THIS
 JOB. - ARCHITECT STATES THAT ONLY
 CABINET WORK ADDING A REFRIDGERATOR AND
 NO WORK ON THE CABINET AT THE SINK THIS
 JOB. 7-18-5)