| 2005-07-06 00:00:00 | *************** UNSAT *********** |
| | |
| | 1)NOTE: PLEASE SEE MISSING REQUIRED |
| | LICENSE INFORMATION ON TITLE BLOCK PER |
| | FAC 61G1-16.004, FS 481.219 |
| | PLEASE SEE MISSING CERTIFICATE OF |
| | AUTHORIZATION #. |
| | |
| | 2)NOTE: PLEASE SHOW ALL CIRCUTING FOR |
| | NEW AND CORRELATE WITH A PANEL SCHEDULE |
| | TO BE SUBMITTED. |
| | PLEASE VERFIY CIRCUITING; NEW, EXISTING? |
| | PLEASE SEE 700.12E FOR EM/EXT LT |
| | CIRCUITING. |
| | |
| | 3)NOTE: PLEASE SEE NOTES MENTIONS 2001 |
| | NEC, 1999 NEC, FBC NEC ETC. PLEASE SEE |
| | AS OF JULY 7TH, 2003, WE |
| | ARE UNDER THE 2002 NEC. |
| | PLEASE ADJUST. |
| | |
| | 4)NOTE: PLEASE SEE 2002 NEC 210.8B3 |
| | WHICH REQUIRES ALL 15- AND 20-AMPERE, |
| | 125-VOLT RECEPTACLES IN NONDWELLING-TYPE |
| | KITCHENS TO BE GFCI PROTECTED. THIS |
| | REQUIREMENT APPLIES TO EACH AND EVERY |
| | 15- AND 20-AMPERE, 125-VOLT KITCHEN |
| | RECEPTACLE, WHETHER OR NOT THE |
| | RECEPTACLE SERVES COUNTERTOP APPLIANCES. |
| | |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AHVE AN |
| | AFFECT ON ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ANY OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |