Plan Review Notes
Plan Review Notes For Permit 05070119
Permit Number 05070119
Review Stop E
Sequence Number 1
Notes
Date Text
2005-07-06 00:00:00*************** UNSAT ***********
  
 1)NOTE: PLEASE SEE MISSING REQUIRED
 LICENSE INFORMATION ON TITLE BLOCK PER
 FAC 61G1-16.004, FS 481.219
 PLEASE SEE MISSING CERTIFICATE OF
 AUTHORIZATION #.
 SEE ONE SET CONTAINS SEALED PHOTOCOPIES
 OF ARCHITECT'S SIGNATURE.
 MUST BE ORIGINAL SIGNATURE, FS 481.221
  
 2)NOTE: PLEASE SEE NOTES MENTIONS NEW
 ELECTRICAL FIXTURES ETC TO BE INSTALLED
 ALONG WITH NEW EM/EXT LTS, HOWEVER THIS
 COULD NOT BE LOCATE DON PLANS ALONG WITH
 A FIXTIRE SCHEDULE.
 PLEASE SEE SOME LTS SHOWN AS EXISTING.
 PLEASE VERFIY CIRCUITING; NEW, EXISTING?
 PLEASE SEE 700.12E FOR EM/EXT LT
 CIRCUITING.
  
 3)NOTE: PLEASE SEE NOTES MENTIONS 2001
 NEC. PLEASE SEE AS OF JULY 7TH, 2003, WE
 ARE UNDER THE 2002 NEC.
 PLEASE ADJUST.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AHVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  