| 2005-07-06 00:00:00 | *************** UNSAT *********** |
| | |
| | 1)NOTE: PLEASE SEE MISSING REQUIRED |
| | LICENSE INFORMATION ON TITLE BLOCK PER |
| | FAC 61G1-16.004, FS 481.219 |
| | PLEASE SEE MISSING CERTIFICATE OF |
| | AUTHORIZATION #. |
| | SEE ONE SET CONTAINS SEALED PHOTOCOPIES |
| | OF ARCHITECT'S SIGNATURE. |
| | MUST BE ORIGINAL SIGNATURE, FS 481.221 |
| | |
| | 2)NOTE: PLEASE SEE NOTES MENTIONS NEW |
| | ELECTRICAL FIXTURES ETC TO BE INSTALLED |
| | ALONG WITH NEW EM/EXT LTS, HOWEVER THIS |
| | COULD NOT BE LOCATE DON PLANS ALONG WITH |
| | A FIXTIRE SCHEDULE. |
| | PLEASE SEE SOME LTS SHOWN AS EXISTING. |
| | PLEASE VERFIY CIRCUITING; NEW, EXISTING? |
| | PLEASE SEE 700.12E FOR EM/EXT LT |
| | CIRCUITING. |
| | |
| | 3)NOTE: PLEASE SEE NOTES MENTIONS 2001 |
| | NEC. PLEASE SEE AS OF JULY 7TH, 2003, WE |
| | ARE UNDER THE 2002 NEC. |
| | PLEASE ADJUST. |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AHVE AN |
| | AFFECT ON ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ANY OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |