| Date |
Text |
| 2006-06-25 00:00:00 | *********** UNSAT ************ |
| | |
| | 1) NOTE: PLEASE SUBMIT COMPLETED |
| | ELECTRICAL PLANS FOR NEW SCOPE OF WORK |
| | PER 2002 NEC NFPA-70 |
| | PLEASE SHOW ALL EXISTING OR NEW |
| | ELECTRICAL MEETING RECEPT SPACING, |
| | EGRESS LIGHTING, LIGHTING CONTROLS, |
| | SMOKE DETECTORS INSIDE AND OUTSIDE ALL |
| | SLEEPING RMS, DEDICATED CIRUCITS FOR |
| | KITCHENS, BATHS, APPLIANCES, ETC |
| | PLEASE SEE PLANS INDICATE A NEW SERVICE, |
| | HOWEVER NO ELECTRICAL RISER DIAGRAM WAS |
| | SUBMITTED. PANEL SCHEDULE SHOWING ALL |
| | CONDUCTOR SIZES, OCP ETC. |
| | FBC ADMIN SECT 106.1.2, 106.3.5.4, |
| | 215.5, 110.9,240.4,310.16,210.52,210.11, |
| | 210.70, LS 101 7.8,220.16, 220.31, 408.4 |
| | ETC |
| | NFPA-72,11.5.1.1,11.8.3, |
| | R313 |
| | |
| | 2) NOTE: PLEASE SEE THAT MIN ENERGY |
| | CALCULATIONS REQUIRED AND SHALL BE |
| | SUBMITTEDCORRELATE WITH ELECTRICAL |
| | PLANS. |
| | THESE SHALL ALSO BE SIGNED, DATED AND |
| | SEALED BY THE DESIGN PROFESSIONAL OF |
| | RECORD. |
| | FBC CHAPTER 13 |
| | |
| | 3) NOTE: PLEASE COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS FROM SETS AND ONLY |
| | INSERT NEW REVISED SHEETS INTO SETS FOR |
| | REVIEW AND STAMPING. PLEASE KNOW, AN |
| | REVISED SHEETS WILL BE REQUIRED TO BE |
| | STAMPED THE "HISTORIC REVIEW". |
| | PLEASE SUBMIT ONE COPY OF ANY OLD/VOIDED |
| | SHEETS SEPARATELY FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |