Plan Review Notes
Plan Review Notes For Permit 05070071
Permit Number 05070071
Review Stop E
Sequence Number 1
Notes
Date Text
2006-06-25 00:00:00*********** UNSAT ************
  
 1) NOTE: PLEASE SUBMIT COMPLETED
 ELECTRICAL PLANS FOR NEW SCOPE OF WORK
 PER 2002 NEC NFPA-70
 PLEASE SHOW ALL EXISTING OR NEW
 ELECTRICAL MEETING RECEPT SPACING,
 EGRESS LIGHTING, LIGHTING CONTROLS,
 SMOKE DETECTORS INSIDE AND OUTSIDE ALL
 SLEEPING RMS, DEDICATED CIRUCITS FOR
 KITCHENS, BATHS, APPLIANCES, ETC
 PLEASE SEE PLANS INDICATE A NEW SERVICE,
 HOWEVER NO ELECTRICAL RISER DIAGRAM WAS
 SUBMITTED. PANEL SCHEDULE SHOWING ALL
 CONDUCTOR SIZES, OCP ETC.
 FBC ADMIN SECT 106.1.2, 106.3.5.4,
 215.5, 110.9,240.4,310.16,210.52,210.11,
 210.70, LS 101 7.8,220.16, 220.31, 408.4
 ETC
 NFPA-72,11.5.1.1,11.8.3,
 R313
  
 2) NOTE: PLEASE SEE THAT MIN ENERGY
 CALCULATIONS REQUIRED AND SHALL BE
 SUBMITTEDCORRELATE WITH ELECTRICAL
 PLANS.
 THESE SHALL ALSO BE SIGNED, DATED AND
 SEALED BY THE DESIGN PROFESSIONAL OF
 RECORD.
 FBC CHAPTER 13
  
 3) NOTE: PLEASE COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO SETS FOR
 REVIEW AND STAMPING. PLEASE KNOW, AN
 REVISED SHEETS WILL BE REQUIRED TO BE
 STAMPED THE "HISTORIC REVIEW".
 PLEASE SUBMIT ONE COPY OF ANY OLD/VOIDED
 SHEETS SEPARATELY FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  