| Notes |
| Date |
Text |
| 2006-02-09 00:00:00 | *** PLANS REDLINED** | | | | | | RISER IS A 400A SERVICE, MIN GEC SHALL | | | BE SIZED PER 250.66, 1/0 MIN. | | | | | | REQUIRES A MIN OF 2 GRND RODS/ FOOTER | | | STEEL. | | | 250.50,250.56. | | | FOOTER STEEL WAS REMOVED FROM RISER, | | | HOWEVER THIS IS REQUIRED. |
|